Accessories

A. Gas Log/Lighter Provision
WARNING! Fire and/or Asphyxiation Risk! Use with solid
wood fuel or decorative gas appliance only. Gas fi re gener-
ates fumes.
DO NOT install unvented gas logs
Damper must be locked fully open when gas logs are
installed
A certifi ed gas log lighter or decorative gas log set can be
installed in this fi replace.
Maximum input is 150,000 BTU/hr.
Decorative gas appliance must be certifi ed to ANSI Z21.60
"Standard for Decorative Gas Appliances for Installation
in Vented Fireplaces".
Must be installed in accordance with the National Fuel
Gas Code, ANSI Z223.1.
A gas log set must incorporate a gas shutoff.
Gas log set requires the damper to be locked fully open.
A listed automatic damper system with safety interlock may
be used in this fi replace with only compatible, listed gas log
sets. See damper system manufacturer's instructions.
Knockouts are provided on both sides of the fi replace for
1/2 in. (13 mm) iron pipe.
A locating dimple (see Figure 13.2) is located on both sides
of the fi replace in the molded brick panels for drilling a 1
in. (25 mm) diameter hole for installation of a gas line.
After the panel is installed, drill the hole for the gas line.
Seal panel around pipe with fi replace mortar or a high
temperature, non-combustible sealant.
B. Wood Burning Inserts
WARNING! Risk of Fire! Improper installation of wood
inserts may cause fi replace or chimney system to overheat.
If a wood burning insert is being installed in this fi replace,
Hearth & Home Technologies recommends full reline of the
chimney.
Cooling air openings at the top of the chimney must not
be obstructed in any manner.
Hearth & Home Technologies recommends securing the
reline at the top of the fl ue and using the cap certifi ed for
use with this fi replace system.
48
Heat & Glo • RUTHERFORD-36 • 4059-341 Rev D • 03/09
Firebox
Refractory
Seal with
fireplace mortar
or non-combust-
ible sealant
Gas line
Repack
insulation
knockout
4 in.
(102 mm)
Figure 13.1 Gas Line Installation
Figure 13.2 Gas Line Dimples
Outer shell
of fireplace
Maintain air clearance
to combustibles.
Combustible
materials
1 1/2 in. (38 mm)
air space around
pipe
Gas line
Combustible materials
may be located at zero
clearance to gas line
beyond 4 in. (102 mm)
from fireplace side.
Gas Line
Dimple
Gas Line
Dimple