Leaving water temperature control

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually or through
the schedule timer or weather dependent (automatic).
Selecting space heating operation
Use the y button to switch ON/OFF space heating (h).
1
Icon h appears on the display as well as the corresponding
water temperature set point.
The operation LED 0 lights up.
Use the ébi and ébj buttons to set the desired leaving
2
water temperature.
Temperature range for heating: 25°C~80°C (leaving water
temperature)
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (see operation range).
Refer to "Remote controller schedule timer" for setup of the schedule
timer function.
NOTE
When an external room thermostat is installed,
the thermo ON/OFF is determined by the external
room thermostat. The remote controller is than
operated in the leaving control mode and is not
functioning as a room thermostat.
The remote controller ON/OFF status always has
priority over the external room thermostat!
Selecting weather dependent set point operation
When weather dependent operation is active, the leaving water
temperature is determined automatically depending on the outdoor
temperature: colder outdoor temperatures will result in warmer water
and vice versa. The unit has a floating set point. Activating this
operation will result in a lower power consumption than use with a
manually fixed leaving water set point.
During weather dependent operation, the user has the possibility to
shift up or down the target water temperature by a maximum of 5°C.
This shift value is the temperature difference between the
temperature set point calculated by the controller and the real set
point. E.g. a positive shift value means that the real temperature set
point will be higher than the calculated set point.
It is advised to use the weather dependent set point because it
adjusts the water temperature to the actual needs for space heating.
It will prevent the unit from switching too much between thermo ON
operation and thermo OFF operation when using the remote
controller room thermostat or external room thermostat.
NOTE
During this operation, instead of showing the water
temperature set point, the controller shows the shift
value which can be set by the user.
Press the ba button 1 time to select weather dependent set
1
point operation (or 2 times when the remote controller room
thermostat function is used).
Icon a appears on the display as well as the shift value. The
shift value is not shown in case it is 0.
Use the ébi and ébj buttons to set the shift value.
2
Range for the shift value: –5°C to +5°C
Icon a will be displayed as long as the weather dependent set
point operation is enabled.
3
Press the ba button to deactivate weather dependent set point
operation.
The ébi and ébj buttons are used to set the leaving
water temperature.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61264-1A – 10.2010
Field settings define the parameters for the weather dependent
operation of the unit. Refer to
detailed description how to set one or more field settings.
T
t
Lo_Ti
Hi_Ti
Lo_A
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
Shift value
= Shift value
[3-00]
Low
ambient
temperature.
[3-01]
High
ambient
temperature.
[3-02] Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature
equals or drops below the low ambient temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[3-03] Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature
equals or rises above the high ambient temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
If by mistake the value of [3-03] is set higher than the
NOTE
value of [3-02], the value of [3-03] will always be used.
"4.15. Field settings" on page 19
+ 05
00
Shift value
– 05
Hi_A
T
A
temperature
(Lo_A):
low
temperature
(Hi_A): high
Operation manual
for a
outdoor
outdoor
6