Sq 60-65 - Direct Drive - Greenheck SQ Brochure & Specs

Centrifugal inline fans direct and belt drive
Table of Contents

Advertisement

SQ 60-65 - Direct Drive

1
(25)
*8
7
8
(225)
12
(305)
Damper size = 9 x 9
(229 x 229)
Unit weight** = 26
(12)
Housing thickness = 20 ga
Outlet velocity = 1.828 x cfm
Dimensions shown in inches (millimeters) and weight is
shown in pounds (kilograms).
*May be greater depending on motor.
**Weight shown is largest cataloged Open Drip Proof motor.
Model Number
SQ-60-E
SQ-60-G
SQ-60-D
SQ-65-E
SQ-65-G
SQ-65-D
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound ratings shown are loudness values in fan sones at 1.5 m (5 feet) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation
type B: free inlet hemispherical fan sone levels.
12
(305)
13
(330)
Motor
Fan
HP
RPM
0
CFM
126
1/140
1050
BHP
0.005
Sones
1.7
CFM
156
1/80
1300
BHP
0.01
Sones
2.5
CFM
186
1/40
1550
BHP
0.017
Sones
4.0
CFM
154
1/100
1050
BHP
0.007
Sones
2.1
CFM
191
1/50
1300
BHP
0.013
Sones
2.9
CFM
228
1/30
1550
BHP
0.022
Sones
4.2
0.45
110
100
0.40
90
0.35
80
0.30
70
0.25
60
50
0.20
40
0.15
30
0.10
20
0.05
10
0
0.00
0
50
0
50
100
150
CFM / Static Pressure in Inches wg
0.05
0.1
0.125
0.15
101
78
63
42
0.006
0.007
0.007
0.006
1.7
1.8
1.8
1.9
135
117
109
99
0.011
0.012
0.012
0.013
2.5
2.5
2.5
2.5
168
153
145
138
0.018
0.019
0.02
0.02
4.0
4.0
4.0
4.0
129
98
79
56
0.008
0.009
0.009
0.008
2.0
2.0
1.9
1.9
171
149
137
123
0.014
0.016
0.016
0.017
2.9
2.9
2.9
2.9
213
194
184
175
0.023
0.026
0.026
0.027
4.1
4.1
4.0
4.0
RPM
Density 0.075 lb/ft
100
150
200
cfm
200
250
300
350
400
3
m
/hr
0.2
0.25
0.3
0.35
72
37
0.013
0.012
2.5
2.5
122
105
78
47
0.022
0.022
0.021
0.02
4.0
4.0
4.1
4.1
92
52
0.016
0.015
2.8
2.8
153
128
101
66
0.028
0.028
0.027
0.025
3.9
3.8
3.7
3.6
3
250
0.375
31
0.019
4.1
46
0.023
3.5
11

Advertisement