Recirculation Application - Bosch GWH C 800 ES Installation Instructions Manual

Temperature modulated with electronic ignition suitable for heating potable water - not approved for space heating purposes intended for variable flow applications
Hide thumbs Also See for GWH C 800 ES:
Table of Contents

Advertisement

Connecting the pressure relief valve (PRV)
A listed pressure relief valve supplied with the heater
must be installed at the time of installation. No valve is
to be placed between the PRV and the heater. No
reducing coupling or other restriction may be installed
in the discharge line. The discharge line must be a
minimum of 4" above a drain and installed such that it
allows complete drainage of both the PRV and the line.
The discharge line must be placed where it will not
cause any damage.
The location of the PRV must be readily accessible for
servicing or replacement, and be mounted as close to
the water heater as possible. See Fig. 16. To install the
PRV, a suitable fitting connected to an extension on a
"T" fitting can be sweated to the hot water line.
Support all piping.
Pressure
relief
valve
Fig. 16 Plumbing Connections (with shutoff valves)
and Pressure Relief Valve
Warning:
In
applications
temperature can exceed 140°F (60ºC), a
3-way valve or mixing valve must be
installed before the appliance to prevent
water exceeding 140°F (60°C) from
entering the appliance.
6 720 608 643
where
inlet
water
3.9

Recirculation application

The GWH C 800 ES Protankless water heater is
approved for domestic hot water recirculation. The
following drawing is provided to outline one possible
recirculation design using the water heater in
conjunction with an Ariston mini tank water heater.
Recirculation directly through the tankless water heater
is also allowed. This schematic is for illustration only and
must not be used for actual Installation without
appropriate engineering and technical advice from a
properly licensed professional in the locality where the
installation is made.
Ariston Minitank
Fig. 17 Recirculation application
1
Full port isolation valve
2
Circulator pump on timer
3
Check valve
4
PRV
5
Expansion tank
The use of a small electric mini-tank after heater (4-6
gallon size) should be used for this application and
designed so the pump will circulate the water through
the mini-tank and the building's hot water return loop
only. Timed or thermostatically controlled operation of
the pump is commonly done. Contact Bosch Water
Heating if further information is needed.
Installation instructions
GWH
C 800
ES
13