Midea MSC-09HRDN1-QD0(E) Service Manual page 31

Dc inverter split wall-mounted type
Hide thumbs Also See for MSC-09HRDN1-QD0(E):
Table of Contents

Advertisement

2)
If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127 seconds
with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is available.
3)
If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti-cold-wind is
disabled.
9.7.2
Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.3
After 7minutes start the operation frequency of compressor submits to following rule:
1) When the machine runs, if ∆Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Zone B: Elevate or keep or descend current frequency.
Zone H: Compressor stops after running with F1 for 60 minutes or when ∆Th>6℃.
2) Temperature difference (∆Tcon) choice.
After power on, the machine will self-diagnose, and if there are no J1 and J2 jump wires, ∆Tcon will be set
as 0℃.
44
38
37
34
33
24
17
2.5
2.0
1.5
1.0
5.0
4.5
1.0
0.5
Remark: ∆Tcon can be changed among 0, -2,- 4 , the default is 0
setting fan speed
low fan
breeze
super breeze
fan stop
low
medium
high
H
B
A
28

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msc-12hrdn1-qc6(e)Msh-12hrdn1-qc6(e)Msh-09hrdn1-qd0(e)

Table of Contents