Ordering Information - Honeywell C7915A Information

Infrared flame detector
Table of Contents

Advertisement

C7915A INFRARED FLAME DETECTOR
Coaxial Cable
Model
C7915A1010
C7915A1036
C7915A1028
a
With 0.125 in. (3.175 mm) diameter hexagonal orifice to reduce the detector field of view.
b
To insulate the detector from sight pipe temperatures higher than -40°F–125°F (-40°C–52°C) and up to 250°F (121°C).
c
To mount the detector on a 1/2 in. sight pipe, specifically to replace Fireye™ lead sulfide infrared flame detectors.
WIRING CONNECTIONS
Nominal 48 in. (1.22 m) coaxial cables—rated for 194°F
(90°C); terminated—one blue and one white.
Coaxial cables enclosed in flexible metal cable—3/8 in. (9.6
mm) maximum outer diameter.
DIMENSIONS: See Fig. 1.
SIL 3 CAPABLE:
The C7915 when used with a R7852B Ampli-check amplifier
in Relay Module EC7810A, 20A, 30A, 40L, 50A;
RM7800[E,G,L,M], 30A, 38[A,B,C], 40[E,G,L,M] 50A,
90[A,B,C,D], 97[A,C], 98A is SIL 3 Capable in a properly
designed Safety Instrumented System. See form number
65-0312 for Certificate Agreement.
APPROVALS:
Underwriters Laboratories Inc. listed: File No. MP268.
Canadian Standards Association certified: Master file LR-
95329-1.
Factory Mutual approved.
Swiss Re (formerly Industrial Risk Insurers): acceptable.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
65-0292-06
Table 1. Models Available
Length
(in.)
(m)
Lead Sulfide Cell
30
0.76
32007255-001
96
2.44
32007255-001
48
1.22
32007255-001
Components Included
105134
50019469-001
Orifice
Bushing With
Magnifying Lens
Plate
X
X
X
X
X
X
IMPORTANT:
Caution, stickers, form 96-610, are included with the
C7915A. Underwriters Laboratories Inc. requires that
this sticker be placed on any junction box in which
C7915A coaxial cables are connected. The sticker
prohibits routing any other wiring through the junction
box.
REPLACEMENT PARTS:
32007255-001 Lead Sulfide Photocell
50019469-001 Bushing with Focusing Lens
105061 Heat Block to insulate the detector from sight pipe
temperatures higher than 125°F (52°C) and up to 250°F
(121°C).
390427A Reducer Bushing, to mount the detector on a 1/2 in.
sight pipe; specifically to replace Fireye™ lead sulfide infra-
red flame detectors.
ACCESSORIES:
105172A Seal-Off Adapter; with glass window to prevent hot
gases from reaching the lead sulfide photocell.
118367A Swivel Mount; provides adjustable positioning of the
C7915A.
Hookup Cable—R1298020; 2-wire, heat- and moisture-resis-
tant, No. 20 AWG, Teflon (TFE) insulated; rated up to
400°F (204°C) for continuous duty; tested for operation up
to 600 volts and breakdown up to 7500 volts.
2
390427A
105061
Reducer
a
b
Heat Block
Bushing
X
X
c

Hide quick links: