Download Print this page

Specifications; Ordering Information - Honeywell C7061A Product Data

Dynamic self-check ultraviolet flame detector
Hide thumbs Also See for C7061A:

Advertisement

C7061A,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances. Therefore, this unit
may not exactly match the specifications listed. This
product is tested and calibrated under closely
controlled conditions, and minor differences in
performance can be expected if those conditions are
changed.
Models:
C7061A Dynamic Self-Check Ultraviolet Flame Detector.
C7061F Dynamic Self-Check Ultraviolet Flame Detector.
(Same as C7061A except with explosion-proof housing for
use in hazardous locations).
Electrical Ratings:
Voltage and Frequency:
The C7061 is powered from the Flame Safeguard unit that
delivers the necessary voltages to operate the tube and
shutter.
Ambient Operating Temperature Ratings
(Outside the Case): -40°F to 175°F (-40°C to 80°C) using
part no. 129464N UV Sensing Tube.
Storage Temperature Ratings: -60°F to 175°F
(-50°C to 80°C).
Housing:
C7061A:
Violet, cast-aluminum cover. Separate mounting flange
(with heat block) and faceplate provide heat insulation
and sealoff.
Meets NEMA 4 enclosure requirements (indoor, outdoor
protection; rain-tight, dust-tight, hose-directed water
protection).
Optional water jacket available; see Accessories.
C7061F: Explosion-proof, two-piece, violet, cast aluminum.
Pressure Rating of Quartz Viewing Window:
C7061A: 20 psi (138 kPa), see Replacement Parts.
C7061F: 100 psi (690 kPa).
Pressure Rating of Quartz Focusing Lens: 20 psi
(138 kPa), see Accessories.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0223—07
Mounting: C7061A: Mounting flange with 3/4 NPT internal
threads for attaching to sight pipe.
C7061A1046: Mounting flange with 1 inch NPT internal
threads for attaching to sight pipe.
C7061F: Pipe union with 1 inch NPT internal threads for
attaching to sight pipe.
Wiring Connections:
Leadwire: NEC Class 1 color coded.
Length: 8 ft (2.4m).
Threaded Leadwire Faceplate Opening: 1/2-14 NPSM
internal threads for attaching conduit.
Connector: C7061A1038 and C7061A1046: Brad Harrison®
41310.
Dimensions: See Fig. 1.
Weight:
C7061A: 2.6 lbs (1.2 kg).
C7061F: 14.5 lbs (6.6 kg).
Serviceability:
C7061A: Field replaceable ultraviolet sensing tube viewing
window, coil and shutter assembly gaskets.
C7061F: Field replaceable self-checking coil and shutter
assembly.
SIL 3 Capable:
The C7061A or F when used with a R7861 self-check ampli-
fier in Relay Module EC7810A, 20A, 30A, 40L, 50A;
RM7800[E,G,L,M], 30A, 38[A,B,C], 40[E,G,L,M] 50A,
90[A,B,C,D], 97[A,C], 98A is SIL 3 Capable in a properly
designed Safety Instrumented System. See form number
65-0312 for Certificate Agreement.
Approvals:
Underwriters Laboratories Inc. Listed: File Number MP268,
Guide Number MCCZZ.
Canadian Standards Association Certified: Master File
LR95329-1.
Factory Mutual Approved: 14740.01.
SwissRe (formerly Industrial Risk Insurers) Acceptable.
C7061F: For use in hazardous locations; Class I, Groups C
and D; Class II, Groups E, F, and G; File no. E34649.
Replacement Parts:
All Models:
129464N Ultraviolet Sensing Tube; -40°F (-40°C).
2

Hide quick links:

Advertisement

loading

This manual is also suitable for:

C7061f