ES Standby Generator System - 7 kW
Transfer Switch Features
• Electrically operated, mechanically-held
contacts for fast, positive connections.
4 of 5
• Rated for all classes of load, 100%
equipment rated, both inductive and
resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• NEMA 1 (indoor rated) enclosure is standard.
• Flush mountable.
Dimensions
Mechanical Dimensions (in inches/mm)
Wire Ranges
Model
No. of Poles
Current Rating (Amps)
Voltage
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
Return to Utility*
Exercise weekly for 12 minutes*
UL Listed
Total of Pre-wired Circuits
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
Weight (Pounds/Kilos)
*Function of Controller
Height
Amps
H1
H2
18.5 in
23 in
10.5 in
50
470 mm
584 mm
267 mm
Amps
Neutral Lug
50
2/0 - #14
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
Width
Depth
W1
W2
15.38 in
3.4 in
391 mm
86 mm
Ground Lug
2/0 - #14
features and benefits
005888-0
2
50
120/240 1Ø
80%
60%
approx. 15 sec.
Standard
Standard
8
5
1
-
1
-
-
10,000
25/11.3
W2
H2
D
W1
H1
Need help?