Modem Retry Interval B
788
Modem Retry Count A
Note: Item 334 must be reset after a Scheduled Call-In; otherwise, the recorder will not call
again.

Alarm and Scheduled Call-In

The ERX Recorder, if configured, can initialize a call-in due to an alarm and a scheduled-call-in.
In this method, item 338 (Scheduled Call-In Occurred) may be used by the host system to
determine whether the call-in was triggered by an alarm or due to a scheduled call-in. A
scheduled call-in will have changed item 338 from '0' to '1' indicating that a scheduled call-in
occurred and not an alarm. Item 338 must have its value reset to a value of '0' and item 334 must
be reset for the next scheduled call-in date after a Scheduled Call-In; otherwise, the recorder will
not call again.
To use this method, set the following items:
Item
333
Call-In Trigger
334
Scheduled Call-In Date
335
Scheduled Call-In Time
339
Scheduled Call-In Phone #
789
Modem AT Enable
780
Modem Init String
781
Modem Dial String
784
Alarm Call-In Phone#
782
Modem Hang-up String
786
Modem Retry Interval A
787
Modem Retry Interval B
788
Modem Retry Count A

Modem Power Control--Call-out Window

Modem power control is used to conserve battery power by only applying power to a
communication device within an operating window when communication is desired. Modem
power control utilizes the alarm output channel of TB1; A- and A+ to control the power applied
to a communication device, such as, a modem, CDPD, or radio, etc.
Item 484, Alarm-Channel-Control must be configured to Modem Power control instead of the
default Alarm Pulse output. This action defeats Alarm Pulse output.
The period that the communications device is powered is controled by item 791 Call-out Start
Time and item 783 Call-out Stop Time and further defined by item 792 Call-out Repeat
Interval and item 793 Call-out Keep Alive Time.
www.honeywell.com
28
Default: 5
Time (minutes) to wait before trying again if all
short-term retries have failed
Default: 1440
Number of short-term retries
Code
Set to
3
Alarm & Scheduled Call-In
Date of call
Time of call
Phone number to call at schedule time
1
Call-In via AT commands
Initialization command of the Modem
Default: ATE0Q0V0X4
Command sent to indicate dialing
Default: ATDT
Phone number to call due to an alarm
Command sent to modem for hang-up
Default: ATH
Time (minutes) between short-term retries
Default: 5
Time (minutes) to wait before trying again if all
short-term retries have failed
Default: 1440
Number of short-term retries