Rf Specifications; Ipgsm-Dp Specifications - Honeywell IPGSM-DP Installation And Setup Manual

Commercial fire communicator
Table of Contents

Advertisement

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

RF Specifications

Transmission
Frequency
Band
GSM 850
824-849
GSM 900
890-915
GSM 1800
1710-1785
GSM 1900
1850-1910

IPGSM-DP Specifications

ITEM
Cabinet Dimensions:
Transformer: N8167
Battery:
Battery Charging Current:
Supervision:
Transmit
Power
(MHz)
(dBm)
33
33
30
30
SPECIFICATION
Width = 12 3/4 inches
Height = 14 7/8 inches
Depth = 3 inches
Primary – 120VAC, 60Hz
Secondary – 18VAC, 50VA
12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.
maximum 1A
The AC power, backup battery, IP communications, and GSM
communications are monitored.
Receive
Receive
Frequency
Sensitivity
(MHz)
(dBm)
869-894
-107
935-960
-107
1805-1880
-106
1930-1990
-105.5
– 11 –
Number
Channel
of
Spacing
Channels
(MHz)
124
200
124
200
374
200
299
200
Duplex
Separation
(kHz)
45
45
95
80

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ipgsm-dpc

Table of Contents