Download Print this page

Specifications - Honeywell V-PLEX 5192SD Manual

Advertisement

5192SD/5192SDT
V-PLEX™ SMOKE DETECTOR

SPECIFICATIONS

Installation
The 5192 Series smoke detectors are
supplied with a convenient mounting
bracket that allows the detector to
be mounted to a variety of electrical
junction boxes. A removable terminal
block, that accepts 14 to 22 gauge wire
to provide easy wiring connections. The
detectors are designed to meet
all applicable requirements for UL
Commercial and Residential Fire
installations as well as NFPA 72
requirements when installed in
compliance with the National
Electric Code and approved/listed control
panels.
DIP
SWITCH
REMOVABLE
TERMINAL BLOCK
Wiring diagram for 5192SD/SDT smoke detector
CompatibilIty
These smoke detectors are compatible
with all VISTA control panels that support
V-Plex (addressable) polling
loop technology. The detectors support
DIP switch or serial number addressing.
DIP switch configuration are compatible
with 5140XM, VISTA-40, and
VISTA-50P controls.
ORDERING
5192SD
Addressable Photoelectric Smoke Detector
5192SDT
Addressable Photoelectric Smoke Detector with Integral Heat Sensor
For more information: www.honeywell.com/security/hsc
Automation and Control Solutions
Honeywell Security & Communications
2 Corporate Center Dr. Suite 100
Melville, NY 11747
1.800.467.5875
www.honeywell.com
Serial number addressing is supported on
VISTA-32FB, 128BP, 128FBP, 250BP,
250FBP, 100-24 and FAP FA1600C,
FA1660C and FA1700C controls. (Refer to
control panel and smoke detector
installation instructions for details.)
Automatic Maintenance
Reporting Compatibility
The automatic maintenance feature is
compatible with the following control
panels:
– VISTA-32FB
– VISTA-128BP
– VISTA-128FBP
– VISTA-250BP
– VISTA-250FBP
– FA1600C
– FA1660C
– FA1700C
The automatic maintenance may be
disabled for all other controls that
do not support this feature. Refer
to control panel and smoke detector
Installation Instructions for details.
Electrical:
• System voltage range: 7-14 V
Standby current (maximum @ 12V):
– LED off: 1.2mA
– LED on: 2.8mA
L/5192/D
May 2009
© 2009 Honeywell International Inc.
Mechanical:
• Diameter: 5.5 inches (140mm) (including
mounting bracket)
• Height: 1.7 inches (43mm)
(including mounting bracket)
• Weight: 5.3 ounces (150 grams)
Environmental:
• Installation temperature range:
32° to 100°F (0° to 38°C)
• Installation humidity range:
10% to 93% RH, non-condensing
• Heat sensor (5192SDT only):
135°F fixed temperature
electronic thermistor
• EMI: Meets or exceeds the
following requirements:
– FCC Part 15, Class B Device
– IEC EMC Directive
Agency Listings
• UL268 Commercial System
Smoke Detector
• Meets UL 217 Requirements
for Residential

Advertisement

loading

This manual is also suitable for:

V-plex 5192sdt