IPGSM-DP Trouble Detection Information

Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the
IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to
report events if there are no faults in the iGSM Communications module.
Fault Condition
PowerBoost1 fault
iGSM Communications Module fault
Failure of one of the two
communications paths.
Failure of both communications
paths.
Dialer Capture Module buffer is full.

Dialer Capture Module Information

LED Indicator
RED – Steady ON
RED – Flashing
GREEN – Steady ON
GREEN – Blinks every 2 sec.
GREEN – Blinks twice every sec.
GREEN – Blinks 10 times every sec.

LED Display Information

Panel Status
RADIO TROUBLE
LOW BATTERY
AC LOSS
AC ON
Indication to Fire Panel
Telco 2 is cut.
Telco 2 is cut.
Telco 1 and 2 are cut.
Hang up. (Panel will retry, giving the buffer a chance to empty.)
STATUS
Messages exist in buffer.
No messages to be sent. Waiting for messages.
Normal Indication.
PowerBoost1 communication problem.
Communication Module connection is lost.
PowerBoost1 and Communications Module connection is lost.
RED
GREEN
Dialer Capture Module
LED Indicator
Yellow – ON when radio trouble is present.
Buzzer – Upon loss of AC power, this will
beep once every 10 seconds.
Yellow – ON when battery is low.
Yellow – (not used)
Yellow – ON when no AC is present.
Green – ON when AC is present.
Note: Telco ports 1 (primary dialer)
and 2 (secondary dialer) may be
used instead of the terminal board.
Whichever connection method is
used, both Telco paths must be
connected to the Fire Panel.