Connecting 3-Phase Input Power - Unitor UWI 400 Owner's Manual

Arc welding power source 380/440 volt model
Hide thumbs Also See for UNITOR UWI 400:
Table of Contents

Advertisement

4-9. Connecting 3-Phase Input Power

3
6
OM-202 137 Page 20
3
4
1
= GND/PE Earth Ground
7
2
L1
5
L2
L3
1
!
Installation must meet all National
and Local Codes − have only quali-
fied persons make this installation.
!
Disconnect and lockout/tagout in-
put power before connecting input
conductors from unit.
!
Always connect green or green/
yellow
conductor
to
grounding terminal first, and never
to a line terminal.
For Three-Phase Operation
1
Input Power Cord.
2
Disconnect Device (switch shown in
the OFF position)
3
Green Or Green/Yellow Grounding
Conductor
4
Disconnect Device Grounding
Terminal
5
Input Conductors (L1, L2 And L3)
6
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1, L2, and L3
to disconnect device line terminals.
7
Over-Current Protection
Select type and size of over-current
protection using Section 4-8 (fused dis-
connect switch shown).
Close and secure door on disconnect
device. Remove lockout/tagout device,
and place switch in the On position.
Tools Needed: