3-9. Connecting 1-Phase Input Power For 230 VAC
3-10. Connecting To 1-Phase Engine Generator w/230 Volt Output
Installation must meet all National and Local Codes − have only qualified persons make this installation.
.
Obtain a 230 volt plug that matches the receptacle on the engine generator. Install the plug on the cord of the welding power source according
to the plug manufacturer's instructions.
Generator Requirements
Engine generator must provide the correct input amperage (see Section 3-8).
Peak voltage must be less than 423 volts AC
RMS voltage must be greater than 180 volts AC.
Frequency must be between 50 and 60 Hz
NOTICE − Make sure welding power source is off during engine generator start-up. Do not turn on the welding power source until the generator has
reached normal operating speed.
OM-250 147 Page 12
1
5
2
3
Installation must meet all National
and Local Codes − have only
qualified
installation.
Disconnect
=GND/PE
input power before connecting
Earth Ground
input conductors from unit.
7
Always connect green or green/yel-
low conductor to supply grounding
terminal first, and never to a line
terminal.
.
See Section 3-10 for information on
connecting unit to an engine generator.
4
1
Black And White Input Conductor (L1
And L2)
2
Green Or Green/Yellow Grounding
6
Conductor
3
Input Power Cord.
4
Disconnect Device (switch shown in
L1
the OFF position)
1
L2
5
Disconnect Device Grounding
Terminal
6
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1 and L2 to dis-
connect device line terminals.
7
Over-Current Protection
Select type and size of over-current
protection using Section 3-8 (fused
disconnect switch shown).
Close and secure door on disconnect
device. Remove lockout/tagout device, and
place switch in the On position.