GE P485 Instruction Manual page 64

Modbus to profibus converter
Table of Contents

Advertisement

APPLICATION EXAMPLE
9–8
3.
Select the
PQMII.D01
4.
The software will display a list of the most commonly used parameters configured for
the PQMII.
Figure 9-9: Parameters configured for PQMII
5.
The Modbus User Map values are already present in the configuration file; as such, it is
not required to create the new parameters. However, it is necessary to save number of
registers to be read. Change the data length to 7 words as required.
6.
Similarly, load the configuration file for MM2 by clicking the Load Device button and
selecting the
MM2-MM3.DO1
Figure 9-10: Parameters configured for the MM2
7.
The software will display a list of the most commonly used parameters configured for
the MM2. The Modbus User Map values are already present in the configuration file; as
such, it is not required to create the new parameters. However, it is necessary to save
number of registers to be read. Change the data length to 5 words as required.
8.
The Motor Start A command and Motor Stop command can be executed using
command function + operation code.
9.
Save this device configuration by clicking the Save Device button.
10. Click Next to proceed to step 4 of the configuration wizard.
file from the list and click on Open.
file.
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE