Note: Controllers that can directly connect to 20-inch cable already has a cable connector on it,
which is same as the J1 connector as shown in Figure 2 (Remote Extender Board).

Important Pre-installation Considerations

Warning: Always ground yourself and/or use a ground strap before touching the RAID controller or
the Intel
safe workstation. Use an ESD-safe Phillips* screwdriver set to a maximum torque of 2.25
inch-pounds, and be sure the screwdriver is centered in the screw to avoid damaging the
screw head. If you exceed the maximum torque specification, you may damage the board,
connectors, or screws, and you will void the warranty of the board.
The batteries in the Intel
hours during fast charge, under normal operating conditions.
To protect your data, Intel recommends that you set the RAID Controller Write Policy to
write-through until the battery unit is fully charged. When the battery unit is charged, you
can change the Write Policy to write-back to take advantage of the performance
improvements of data caching.
The maximum ambient temperature for the battery pack is shown in the following tables.
®
Intel
RAID Smart Battery AXXRSBBU8 User's Guide
Table 1. Cable Compatability
RAID Controller or Server System
®
RAID Smart Battery AXXRSBBU8. Perform all installation work at an ESD-
®
RAID Smart Battery AXXRSBBU8 must charge for at least six
AXXRSBBU8 Operating temperature of 55°C
Expected hold time
Service life
AXXRSBBU8 Operating temperature of 45°C
Expected hold time
Service life
20-inch Cable
X (Requires the REB)
X (Requires the REB)
X (Direct connection with controller without REB)
X (Direct connection with controller without REB)
X (Direct connection with controller without REB)
X (Direct connection with controller without REB)
48 hours
12 hours
Up to 1 year
Up to 3 years
48 hours
12 hours
Up to 3 years
Up to 5 years