Approvals:
Underwriters Laboratories Inc.: UL873 listed.
Flammability Rating: UL94-5VB.
Plenum Rated.
CE.
C-tick.
Accessories:
4074EJM Bag Assembly. Consists of: Checkout jumper,
620 ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm checkout
resistors.
C7046A Discharge Air Temperature Sensor.
C7150B Mixed Air Temperature Sensor.
C7232A,B Carbon Dioxide Sensors.
C7400A Solid State Enthalpy Sensor for use with W7212A,
W7213 and W7214.
C7400C for use with W7212C models.
C7660 Dry Bulb Temperature Sensor.
S963B1128 Remote Potentiometer to provide remote control of
damper minimum position.
ST6008 Energy Management Timer for occupied/unoccupied
control.
2-1/16
(53)
1-15/16
(49)
1/8 (4)
2-5/8 (66)
Fig. 1. Logic module dimensions in in. (mm).

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
4-3/8 (112)
1-5/8
(41)
4-1/8
(104)
M20578A
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
5. When adding a CO2 sensor (DCV sensor) in the field,
the MIN POS and DCV MAX position potentiometers
must be adjusted by the installer. The MIN POS potenti-
ometer must be closer to the fully CCW position that the
DCV MAX potentiometer for the damper to modulate
beteen the two settings on a call for DCV.

Location and Mounting

The logic modules mount on an M7215 or a sheet metal duct
or panel. When planning the installation, allow enough
clearance for maintenance and service (see Fig. 1 for
dimensions). Mount device in a location protected from rain,
snow, and direct sunlight. Secure device to sheet metal using
the two supplied mounting screws, see Fig. 3.
CAUTION
Equipment Damage Hazard.
Mounting screws longer than 5/8 in. can damage
internal motor components.
When mounting the module to an M7215 use only the
included #6 5/8 in. thread-forming screw.
NOTE: See Fig. 4 for representative locations of connected
system devices.
M7215 DAMPER MOTOR
ECONOMIZER
LOGIC MODULE
5/8 INCH SCREW INCLUDED WITH LOGIC MODULE.
Fig. 2. Direct mounting of module.