Troubleshooting Guide - Aprilaire 850 Installation & Maintenance Instructions Manual

Steam humidifier fan pack
Table of Contents

Advertisement

TRoUbleSHooTInG GUIDe

If a problem arises with the Aprilaire Model 850 Steam Humidifier Fan Pack, please review the following troubleshooting guide for possible
causes and solutions . If the problem persists, call Aprilaire Tech Support toll-free at 1-800-334-6011 . Please be prepared to describe the exact
nature of the problem .
Table 1 – Troubleshooting Guide
Problem
Possible cause
Water dripping from
Tubing connection
Model 850
Fan not operating
Steam outlets blocked
Foaming in canister or
steam hose
Fan does not operate
Wiring
Model 800 power
No humidity call
Circuit board output
Motor failure
Noise
Fan noise
Gurgling
action
Check all connections .
See "Fan does not operate" .
Clean steam dispersion manifold outlet .
Rinse components with clean water .
Check wiring .
Check that Model 800 is powered and on .
Adjust humidistat setting . Check location of humidistat .
Confirm 24 VAC output from Model 800 FAN PACK terminals during a call for humidity .
Replace fan motor .
Check for obstructions or damage to fan .
Add a drip tee and trap (PN 4028) to the steam line as close to the Model 800 as
possible to divert condensation to drain . See Figure 5 .