Aprilaire 800 Installation & Maintenance Instructions Manual

Aprilaire 800 Installation & Maintenance Instructions Manual

Steam humidifier

Advertisement

Installation & Maintenance Instructions

Table of ConTenTS

Safety Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Materials List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Principles Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specifications & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Choosing A Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
- Dispersion Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
- Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Prepare Humidifier For Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Install Steam Dispersion Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mount Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model 800 Steam Humidifier
ReaD anD SaVe THeSe InSTRUCTIonS
Model 800 Steam Humidifier
Install Steam Hose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Supply Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Automatic Digital Control And Control Wiring . . . . . . . . . . . . . . . . 10
Electrical Power Wiring & Shut-off Switch . . . . . . . . . . . . . . . . . . 11
Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Shut Down Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Checking System operation & Troubleshooting . . . . . . . . . . . . 20
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Advertisement

Table of Contents
loading

Summary of Contents for Aprilaire 800

  • Page 1 Model 800 Steam Humidifier Model 800 Steam Humidifier Installation & Maintenance Instructions Table of ConTenTS Safety Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Install Steam Hose .
  • Page 2: Safety Cautions

    SafeTy CaUTIonS CaUTIon aTTenTIon InSTalleR Read this manual before installing. This product must be installed by qualified HVAC and electrical contractors and in compliance with local, state, federal, and governing codes. Improper installation can cause property damage, severe personal injury, or death as a result of electric shock, burns, or fire. Read all cautions and instructions.
  • Page 3: Principles Of Operation

    Model 800 humidifier one week or more of operation to reach rated capacity, especially if it is wired to operate on 120 volts. when operating on 240 volts, the Model 800 usually will reach nominal capacity within a few hours, even with lower conductivity water.
  • Page 4: Sequence Of Operation

    SeQUenCe of oPeRaTIon When the Automatic Digital Humidifier Control (ADHC) detects RH below the set point, and provided the humidifier is turned on and the HVAC system blower is operating, the internal controller in the humidifier energizes the electrodes and measures the current flowing through the water between them .
  • Page 5 SPeCIfICaTIonS & DIMenSIonS (ConTInUeD) fIGURe 2 – Humidifier & Dispersion Tube Dimensions 3" Mounting Plate 8 7/8" to first opening 1 3/4" Fill Cup 7 7/8" 3" sq 3 3/8" 1 5/8" 1" dia 3 3/8" 4 1/4" 8 1/4" 5 3/4"...
  • Page 6: Installation Instructions

    HVAC system heat call . When installing the humidifier in a system with variable speed blower, determine absorption distance based on airflow at the lowest speed . Call Aprilaire Tech Support at 1-800-334-6011 for additional information on absorption .
  • Page 7 InSTallaTIon InSTRUCTIonS (ConTInUeD) elevation fIGURe 3 – Dispersion Tube Mounted above Humidifier The preferred location for the dispersion tube is higher than the humidifier so that the steam hose has a constant downward Steam hose or pipe. Dispersion tube slope of at least 2” per foot from the dispersion tube to the Insulate pipe with 1”...
  • Page 8: Humidifier

    InSTallaTIon InSTRUCTIonS (ConTInUeD) fIGURe 5 3/4" x 1" Reducing Coupling Dispersion Tube Steam Hose 1-1/2" Hose Clamp 1" Copper Pipe 1-1/2" Hose Clamp Steam Hose Humidifier 90-1527 HUMIDIfIeR fIGURe 6 – Clearances Do not mount humidifier in a location where ambient temperature exceeds 104°f or where freezing temperatures may occur.
  • Page 9: Prepare Humidifier For Mounting

    InSTallaTIon InSTRUCTIonS (ConTInUeD) PRePaRe HUMIDIfIeR foR MoUnTInG Unpack carton . Open front panel by removing screw and lifting panel up and away from humidifier . Disconnect three wires from top of canister by pulling straight up . The two large wires are the electrode conductors . The smaller wire is connected to the high water level sensor . Remove canister by pulling it up and out of drain assembly .
  • Page 10: Drain Line

    . Connect “H” terminals on ADHC to “HUMIDISTAT” terminals on humidifier circuit board . The “H” terminals on the Model 62 provide a dry contact switch to energize the humidifier, if 24V is applied to the Humidistat terminals on the Model 800, the control board will be damaged .
  • Page 11: Electrical Power Wiring & Shut-Off Switch

    With factory settings, the Model 800 draws 11 .5 amps +/- 10% . Use a minimum 20 amp dedicated circuit when installing to operate at 11 .5 amps . The model 800 can be set to draw 16 .0 amps +/- 10% by repositioning dip switch #1 on the control circuit board (see Figure 8) . When set to 16 amps, use a minimum 25 amp dedicated circuit .
  • Page 12 InSTallaTIon InSTRUCTIonS (ConTInUeD) wIRInG InSTRUCTIonS Install disconnect switch (not provided) between line power source and humidifier . Knock-outs for power wiring and low voltage control circuit wiring are located on the top of the humidifier . Connect power and ground wiring as shown in appropriate wiring diagram . • 2 40 VAC – figure 10 • 2 08 VAC – figure 11 • 1 20 VAC – figure 12...
  • Page 13 InSTallaTIon InSTRUCTIonS (ConTInUeD) fIGURe 10 – 240 VaC wiring Diagram NOTE: MODEL 800 IS SHIPPED FROM THE FACTORY WIRED IN MAIN POWER SWITCH THE 240 VOLT CONFIGURATION. (NOT PROVIDED) POWER N, L2 TERMINAL BLOCK POWER RELAY CONTACTS JUMPER WIRE BLK / WHT...
  • Page 14 InSTallaTIon InSTRUCTIonS (ConTInUeD) fIGURe 11 – 208 VaC wiring Diagram NOTE: MODEL 800 IS SHIPPED FROM THE FACTORY WIRED FOR 240 VOLTS. THE BLACK / WHITE WIRE FROM L1 MAIN POWER SWITCH (NOT PROVIDED) MUST BE MOVED TO THE 208 VOLT TERMINAL FOR 208 VOLT OPERATION.
  • Page 15 InSTallaTIon InSTRUCTIonS (ConTInUeD) fIGURe 12 – 120 VaC wiring Diagram NOTE: MODEL 800 IS SHIPPED FROM THE FACTORY WIRED FOR 240 VOLTS. MAIN POWER SWITCH THE BLACK / WHITE WIRE FROM L1 (NOT PROVIDED) MUST BE MOVED TO THE 120 VOLT TERMINAL FOR 120 VOLT OPERATION.
  • Page 16: Start-Up Procedure

    STaRT-UP PRoCeDURe 1 . Once the supply water, drain, steam hose, electrical power and control wiring connections are complete, make sure canister is fully seated into drain valve and three wire connectors on top of canister are secure . (High water probe wire and two interchangeable electrode wires .) 2 .
  • Page 17: Operating Modes

    oPeRaTInG MoDeS When the humidifier is powered and turned on, the “On/Off” light is illuminated green . During fill cycles, the “Fill” light illuminates green . When the humidifier is turned on, any time the ADHC sends a call for humidity, the Steam light illuminates green . Any time the drain valve is activated, the “Drain”...
  • Page 18: Display Panel

    DISPlay Panel Green lights indicate normal operation . Yellow Steam light indicates humidifier is operating at less than rated capacity . Yellow Steam light also indicates humidifier is in Test mode . Flashing red Service light indicates canister has reached the end of its life and needs to be replaced . Solid red lights indicate humidifier has shut down and requires service .
  • Page 19: Maintenance

    . To RePlaCe THe CanISTeR Replace the canister annually and when prompted by the “Service” light . Use Only Genuine Aprilaire Model 80 Canister . 1 . Press On/Off switch to turn humidifier off .
  • Page 20: Checking System Operation & Troubleshooting

    The following troubleshooting guide is intended to help diagnose and resolve general operational problems with Model 800 Humidifier . If a problem persists, call Aprilaire Tech Support toll-free at 1-800-334-6011 . Please be prepared to describe the exact nature of the problem .
  • Page 21 CHeCkInG SySTeM oPeRaTIon & TRoUbleSHooTInG (ConTInUeD) Table 5 – Troubleshooting Guide Problem Possible Cause action General operating Field-wired terminal Check L1, N/L2 and Ground connections . problems . Humidifier connections . Check HUMIDISTAT and FAN PACK Terminal connections . will not turn on or HUMIDISTAT terminals must be connected to an on/off device .
  • Page 22 CHeCkInG SySTeM oPeRaTIon & TRoUbleSHooTInG (ConTInUeD) Table 5 – Troubleshooting Guide (continued) Problem Possible Cause action Water is flowing down drain O-ring is not properly inserted . Remove canister and make sure O-ring is seated in groove in drain valve . while humidifier is making steam (Steam light illuminated green or yellow) .
  • Page 23: Replacement Parts

    RePlaCeMenT PaRTS Parts shown are for Model 800 Humidifiers manufactured after May 2012 (11 .5 and 16 .0 amp capability) . For parts for Model 800 humidifiers manufactured prior to May 2012, refer to Aprilaire Humidifier Replacement Parts & Price List .
  • Page 24 4990 Fill Cup Cap 4975 Membrane Switch 4991 Steam Dispersion Tube & Screws 5306 Universal Transformer, Model 800 Automatic Digital Control for Model 800 4977 Power Relay Steam Canister and O-Ring 4978 Electrode Wire (1) 5308 Transformer Terminal Block 4979...
  • Page 25 Interrupteur 4592 d’admission remplissage 5309 d’écoulement té Siphon 4028 robinet d’alimentation Système étrier à Robinet-valve 4001 purge Robinet 4983 Aprilaire ventilateur Bloc courant détection imprimés circuits Carte 4982 manuel Humidostat 4655 interne contrôle imprimés circuits Carte 4981 numérique manuel Humidostat d’entrée...
  • Page 26 90-1698 pièces . description obtenir pour suivantes pages Reportez-vous Aprilaire . humidificateur pour rechange pièces prix liste à reportez-vous 2012, avant fabriqués modèle humidificateurs pièces Pour ampères) . 16,0 11,5 (capacité 2012 après fabriqués modèle humidificateurs pour sont illustrées pièces ReCHanGe PIÈCeS...
  • Page 27 purge . cycles trois après l'intensité réduire peut nominale capacité au-dessus cartouche . nouvelle installez minéraux dépôts éliminer pour cartouche Rincez à courant capté L'unité continu . rouge service Voyant haut . vers orientés sont dispersion tube tubes petits Assurez-vous conduit .
  • Page 28 cartouche . dans surpression allumé . entraîne vapeur conduite n’est drain figure à Reportez-vous vapeur . conduite points tous dans siphon Installez dans élevée statique pression voyant mais drain, 12 . figure à câblage dans s’écoule diagramme Reportez-vous orientés . correctement solidement fixés...
  • Page 29 Pour TeST MoDe correctement . installé l’humidificateur assurez-vous généraux, fonctionnement problèmes Pour problème . exacte nature décrire à prêt Soyez 1-800-334-6011 . gratuitement composant d’Aprilaire technique service avec communiquez persiste, problème 800 . modèle l’humidificateur avec généraux fonctionnement problèmes résoudre diagnostiquer à...
  • Page 30 (purge) Drain verte Lorsque vider . l’humidificateur Laissez l’humidificateur . éteindre pour marche/arrêt l’interrupteur Appuyez 80 . modèle Aprilaire originales cartouches seulement Utilisez l’indique . vous » Service « voyant lorsque annuellement cartouche Remplacez CaRToUCHe ReMPlaCeR PoUR siphon .
  • Page 31 continu Rouge service . d’un besoin fonctionne L’humidificateur électrodes . entre maximal fonctionnement actuel niveau moins à heures période autre plus heures, pendant fonctionné l’humidificateur lorsque produit clignotant Rouge réduite . capacité à mais fonctionner, à continue L’humidificateur utile . durée atteint cartouche...
  • Page 32 éteint . l’humidificateur s’éteint (purge) Drain voyant lorsque terminé d’évacuation cycle cartouche . l’évacuation pendant minutes quatre pendant vert devient puis secondes, pendant vert clignote (purge) Drain voyant d’évacuation . l’eau tempérer pour s’ouvrira remplissage robinet minutes . quatre d’évacuation cycle commencera L’humidificateur...
  • Page 33 marche . l’humidificateur mettre pour (marche/arrêt) On/Off l’interrupteur Appuyez 10 . approprié . niveau CANH Réglez s’éteint . (purge) Drain voyant lorsque terminé d’évacuation cycle cartouche . l’évacuation pendant minutes quatre pendant vert devient puis secondes, pendant vert clignote (purge) Drain voyant cartouche .
  • Page 34 90-1658 STATIQUE DÉCHARGE TERRE À MISE J10-2 CÂBLE-RUBAN J10-1 D’AFFICHAGE PANNEAU SÉCURITÉ INTERRUPTEUR volts SITE CÂBLAGE CONTRÔLE CIRCUIT CÂBLAGE PURGE ROBINET volts TENSION HAUTE CÂBLAGE J6-2 REMPLISSAGE ROBINET J6-1 volts VAPEUR CARTOUCHE volts D’ALIMENTATION RELAIS BOBINE J1-2 ÉLECTRODE ÉLECTRODE D’EAU NIVEAU J1-1 SONDE...
  • Page 35 90-1659 STATIQUE DÉCHARGE TERRE À MISE J10-2 CÂBLE-RUBAN J10-1 D’AFFICHAGE PANNEAU SÉCURITÉ INTERRUPTEUR volts SITE CÂBLAGE CONTRÔLE CIRCUIT CÂBLAGE PURGE ROBINET volts TENSION HAUTE CÂBLAGE J6-2 REMPLISSAGE ROBINET J6-1 volts VAPEUR CARTOUCHE volts D’ALIMENTATION RELAIS BOBINE J1-2 ÉLECTRODE ÉLECTRODE D’EAU NIVEAU J1-1 SONDE...
  • Page 36 90-1660 STATIQUE DÉCHARGE TERRE À MISE J10-2 CÂBLE-RUBAN J10-1 D’AFFICHAGE PANNEAU SÉCURITÉ INTERRUPTEUR volts SITE CÂBLAGE CONTRÔLE CIRCUIT CÂBLAGE PURGE ROBINET volts TENSION HAUTE CÂBLAGE J6-2 REMPLISSAGE ROBINET J6-1 volts VAPEUR CARTOUCHE volts D’ALIMENTATION RELAIS BOBINE J1-2 ÉLECTRODE ÉLECTRODE D’EAU NIVEAU J1-1 SONDE...
  • Page 37 AMPÈRES 11,5 À AMPÈRES 16,0 À NOMINAL 90-1777 90-1778 NOMINAL FONCTIONNEMENT FONCTIONNEMENT POUR » « POSITION POUR USINE RÉGLAGE À N° COULISSE À COMMUTATEUR VOLTS INSTALLÉ N'EST S'IL APPROPRIÉE BORNE VERS DÉPLACEZ USINE. EFFECTUÉE CÂBLAGE POSITION DANS LIAISON NOIR/BLANC transformateur commutateurs branchement bloc...
  • Page 38 figure à Reportez-vous transformateur. branchement bloc approprié l’onglet vers d’alimentation branchement bloc l’onglet à fixé noir/blanc liaison déplacez volts, utilisez vous CA . volts 120, fonctionner peut mais volts à fonctionnement pour câblé l’usine expédié modèle vapeur à L’humidificateur locaux . codes selon fils...
  • Page 39 4655 n° pièce l’humidostat utilisez conditionné, l’espace dans mural humidostat nécessite l’application endommagée . sera imprimés circuits carte 800, modèle l’humidistat bornes appliqué volts courant l’humidificateur, amorcer pour contact à interrupteur fournissent modèle » « bornes l’humidificateur .
  • Page 40 cartouche . utile durée réduire grandement peuvent genre filtres puisque antitartres temps dans libèrent filtres N’utilisez suspension . solides élevés niveaux ayant régions dans cartouche utile durée augmenter peut ligne particules à filtre d’un l’ajout Remarque robinet . bruit réduire à...
  • Page 41 debout . position niveau verticale surface monté être doit L’humidificateur 90-1519 fibres . conduit panneau l’humidificateur montez stable . structurellement s’il tôle conduit bois surface monté être peut L’humidificateur drain pour 40,6 supérieure . cartouche avec étanche connexion d’assurer permet cela LATÉRALE courbure;...
  • Page 42 117,3 102,2 49,2 121,1 102,2 49,2 121,1 102,2 49,2 121,1 102,2 49,2 124,9 106,0 53,0 124,9 106,0 53,0 124,9 106,0 53,0 124,9 121,1 109,8 102,2 56,8 51,1 128,7 124,9 111,6 106,0 58,7 54,9 128,7 128,7 111,6 109,8 58,7 58,7 218,8 218,8 88,2 88,2...
  • Page 43 être doit dispersion tube l’absorption . supplémentaires renseignements obtenir pour 1-800-334-6011 d’Aprilaire technique service avec Communiquez basse . plus vitesse à d’air flux selon d’absorption distance déterminez variable, vitesse à...
  • Page 44 90-1518 DESSOUS 20,0 d’eau remplissage conduite Connexion Drain ARRIÈRE LATÉRALE AVANT 10,2 53,0 montage 30,5 Trous 10,2 18,1 25,7 DESSUS dispersion Sortie électriques défonçables Alvéoles VAPEUR DISPERSION TUBE diamètre 14,6 20,9 10,8 20,0 remplissage Godet ouverture première vers 22,5 montage Plaque dispersion tube...
  • Page 45 cartouche . l’intérieur à minéraux précipitation raison temps augmentera poids 10,4 l’humidificateur fonctionnement Poids 12,7 l’humidificateur d’expédition Poids 131,0 volts 113,6 volts 16,0 60,6 volts 88,2 volts 77,6 volts 11,5 43,5 volts (litres/jour) vapeur maximale Capacité Tension Intensité l’humidificateur Capacités –...
  • Page 46 . capacité atteindre pour temps plus faudra mais conductivité, faible à l’eau à relié lorsqu’il vapeur produira L’humidificateur 800 . modèle dans bien fonctionnent adoucie l’eau dure étant comme considérée l’eau litre . grains entre varie dureté dont à...
  • Page 47 nécessaire) montage pour Panneaux montage (1,8 vapeur à Boyau extérieur diamètre étrier à Robinet-valve dispersion Tube d’alimentation d’eau Tuyauterie serrage Brides l’humidificateur Câblage numérique automatique Contrôle intérieur diamètre principale d’alimentation Interrupteur d’évacuation Tuyauterie Humidificateur foURnIS foURnIS MaTÉRIaUx MaTÉRIaUx lISTe dommages. causer pourrait condensation...
  • Page 48 – Aprilaire 2012 © B2205753A 4 .12 10009859 U .S .A . Printed • Fax: 608/257-4357 • www.aprilairepartners.com P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 DIReCTIVeS ConSeRVeR lIRe . . . . . . . . . . . . . .

Table of Contents