A 24 Vac Wiring Distances - Bosch TC9346A Series Instruction Manual

Environmental enclosure
Table of Contents

Advertisement

EXAMPLE: An enclosure that re-
quires 80 vA and is installed 35 feet
(10 m) from the transformer would
require a minimum wire gauge of
20 AWG.
NOTE: Distances are calculated in
feet; values in parentheses are
meters.
10
Table A. 24 VAC Wiring Distances
The following are the recommended maximum distances for 24 VAC applications
and are calculated with a 10-percent voltage drop. (Ten percent is generally the
maximum allowable voltage drop for AC-powered devices.)
20
10
283
451
(86) (137) (218) (348) (551) (877)
20
141
225
(42)
(68) (109) (174) (275) (438)
30
94
150
(28)
(45) (72)
40
70
112
(21)
(34) (54)
50
56
(17)
(27) (43)
60
47
(14)
(22) (36)
70
40
(12)
(19) (31)
80
35
(10)
(17) (27)
90
31
(9)
(15) (24)
100
28
(8)
(13) (21)
110
25
(7)
(12) (19)
120
23
(7)
(11) (17)
130
21
(6)
(10) (16)
140
20
(6)
150
18
(5)
160
17
(5)
170
16
(4)
180
15
(4)
190
14
(4)
200
14
(4)
Wire Gauge
18
16
14
12
10
716
1142 1811 2880
358
571
905
1440
238
380
603
960
(115) (183) (292)
179
285
452
720
(86) (137) (219)
90
143
228
362
576
(69) (110) (175)
75
119
190
301
480
(57)
(91) (146)
64
102
163
258
411
(49)
(78) (125)
56
89
142
226
360
(43)
(68) (109)
50
79
126
201
320
(38)
(61)
(97)
45
71
114
181
288
(34)
(55)
(87)
41
65
103
164
261
(31)
(49)
(79)
37
59
95
150
240
(28)
(45)
(73)
34
55
87
139
221
(26)
(42)
(67)
32
51
81
129
205
(9)
(15)
(24)
(39)
(62)
30
47
76
120
192
(9)
(14)
(23)
(36)
(58)
28
44
71
113
180
(8)
(13)
(21)
(34)
(54)
26
42
67
106
169
(7)
(12)
(20)
(32)
(51)
25
39
63
100
160
(7)
(11)
(19)
(30)
(48)
23
37
60
95
151
(7)
(11)
(18)
(28)
(46)
22
35
57
90
144
(6)
(10)
(17)
(27)
(43)