Installation Instructions
(with Plume Management Facility)
CD Easy-Flue 500 mm Part No. 6.2000510
CD Easy-Flue 1000 mm Part No. 6.2001010
1.
GENERAL
Note: These flues MUST ONLY be used with the Alpha Condensing boilers.
a.
The Alpha Easy-Flue is suitable for straight horizontal flues only and can be extended up to the maximum lengths
given in Section 4.
b.
The Alpha CD Easy-Flue is suitable for providing two options for management of the exhaust flue gas/plume emitted
from the terminal. They are:-
i. Divert the plume at 45° by altering the terminal of the the Easy-Flue.
ii. Extend the inner flue duct by using Plume Management accessories to re-locate the terminal to an area where the
plume will not cause a nuisance. Note: When fitting plume management accessories, ensure there is always a
slight slope towards the flue assembly in the wall and there is no part of the pipework where condensate/rain will
collect.
Refer to Section 5 for full details.
c.
The Easy-Flue includes a 90° bend, (no separate 90° bend is required).
d.
Ensure the flue assembly is installed horizontally and the inner flue duct has a slight downward slope towards the boiler.
e.
The flue system must be installed in accordance with BS 5440:1.
f.
The boiler must be installed in accordance with the installation instructions supplied with the Alpha condensing boiler.
g.
The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below.
Note: Where the length is less than the minimum or more than the maximum, refer to Section 4.
Alpha CD Easy-Flue
KIT CONTENTS
CD/HE Boiler
CD Easy-Flue
500 mm
1000 mm
CDR Boiler
CD Easy-Flue
500 mm
1000 mm
Fig. 1 - Rear Flue
B (mm)
CD50 Boiler
CD Easy-Flue
Max
Min
500 mm
510
320
1000 mm
955
745
B Max (mm)
B Min (mm)
13R/18R
24R
13R/18R
515
545
325
960
990
750
B (mm)
Max
Min
440
250
885
675
24R
355
780