CONFIGURING THE IQ PROFILER
LED Disable Jumper
To prevent the walk test LED from turning on, remove the jumper
from the pins labeled LED DISABLE. Removing this jumper will not
affect the flashing of the LED on self test failure.
Sensitivity Setting (SEN Jumper)
The unit is shipped with no jumper in this position. This is the normal
sensitivity mode and is recommended for most installations whose
coverage area does not exceed 30' x 35'. Coverage out to 50' x
50' is possible in this mode, but the intruder will have to cover a
larger distance before detection. To have faster catch performance
this jumper must be installed. Note: Advanced signal processing
will be defeated in this high sensitivity mode. DO NOT INSTALL
THIS JUMPER IF PETS OR RODENTS ARE PRESENT.
COMPLETING THE INSTALLATION
Allow at least three minutes for the unit to stabilize after applying
power, during this time the unit will perform its own self diagnostics
and set a baseline detection level. The LED will flash rapidly for
approximately 1 minute and not function until the unit is ready. If the
unit was installed after being kept in a hot or cold vehicle allow the
unit to operate with its cover in place for about 15 minutes. This will
insure that the unit has measured the proper room temperature.
Walk test the unit to insure the desired coverage, making any board
height adjustments that may be necessary. Note: One common
cause of short range is having the lens in up side down, always
check this! During walk test, the unit will go into a zone finding mode
for 15 seconds after each trip. This will cause the LED to light each
time a beam is entered. To view the normal detection pattern
remain motionless for at least 15 seconds between walk tests.