Installation Guide
Installer setup
Setup functions
0250
2nd stage heat
cycle rate (CPH)
0260
3rd stage heat
cycle rate (CPH)
0270
Emergency heat
cycle rate (CPH)
0280
Continuous
Backlight
0300
Manual/Auto
changeover
0310
Auto changeover
deadband
0320
Temperature
display
0330
Daylight savings
0500
Furnace filter
change reminder
0502
Furnace filter
for Run time
0520
UV Lamp
Replacement
Reminder
69-2486—03
Settings & Options
5
Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
5
Gas or oil furnaces of less than 90% efficiency
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
9
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
9
Electric emergency heat
1
Steam or gravity systems
3
Hot water systems & furnaces of 90%+ efficiency
5
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0
Backlight on for approx. 45 seconds after keypress
1
Backlight always on low intensity, full bright after keypress
(requires 24VAC connection)
Manual changeover (Heat/Cool/Off)
0
1
Automatic changeover (Heat/Cool/Auto/Off)
Heat/cool temperature 3°F apart (1.5°C)
3
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)])
0
Fahrenheit
1
Celsius
1
Auto-change to daylight savings time (through 2007, and for
areas that do not use the new 2008 DST calendar)
0
Daylight savings time is turned off
0
Off
1
10-day run time (about 1 month)
2
30-day run time (about 3 months)
3
60-day run time (about 6 months)
4
90-day run time (about 9 months)
5
120-day run time (about 1 year)
6
180-day run time (about 1.5 years)
7
270-day run time (about 2 years)
8
365-day run time (about 3 years)
9
30 calendar days
10
60 calendar days
11
90 calendar days
12
120 calendar days
13
180 calendar days
14
365 calendar days
0
Counts both heat and cool
1
Counts cool only
0
Disabled
1
365 days
2
730 days
8
(factory default in bold)