7.2 Replacement of fan (fig. 55)
Isolate the boiler from the electrical
supply.
Remove front casing as in section
7.1.3, and remove combustion
chamber cover as in section 7.1.5.
Disconnect the electrical connections
from the fan.
Remove the 2 fan securing screws
(4) and remove fan.
Reassemble in reverse order.
Re-fit combustion chamber and front
casing.
Carry out electrical checks (see
section 5.1).
7.3 Replacement of air pressure
switch (fig. 56)
Isolate the boiler from the electrical
supply.
Remove front casing as in section
7.1.3.
Disconnect electrical connections to
pressure switch
Remove screw (1) and lift out
pressure switch.
Disconnect air tubes (2) from switch.
Reassemble in reverse order.
Carry out electrical checks (see
section 5.1).
Note: Air tubes should be reconnected
P1 to white tube.
P2 to blue tube.
(P1 and P2 are marked on air
pressure switch).
34
4
fig. 55
2
fig. 56
1