5 Operation
5.10.2 Activating emergency mode
Depending on the type of malfunction the expert techni-
cian can set the heat pump to continue operation in
emergency mode (via an integrated electric auxiliary
heating) until the cause of the error is remedied, and ei-
ther for heating operation (display "heating priority"),
for hot water operation (display "hot water priority") or
for both (display "heating priority/hot water priority"),
see the following tables, column "emergency operation".
5.10.3 Errors/malfunctions that you can resolve
Malfunction sign
Possible cause
Noise in the heating
Dirt in the heating
circuit.
circuit.
Faulty pump.
Air in the heating
circuit.
Table 5.4 Other Malfunctions
5.10.4 Warnings
The following warning messages do not cause a mal-
function in the operation of the heat pump. The heat
pump is not shut down.
Take note of the error code and text and discuss this
during the next inspection with the expert technician.
Fault code
Error text/description
26
Overheating on compressor pressure side
36
Low brine pressure
Table 5.5 Warning messages, no shutdown
26
5.10.5 Temporary malfunctions
The heat pump is shut down temporarily and starts up
again independently when the cause of the fault is re-
moved.
Depending on the error the heat pump switches back on
automatically after 5 or 60 minutes.
Take note of the error code and text and discuss this
during the next inspection with the expert technician.
Fault code
20
Solution
Bleeding heating
circuit.
22
27
28
29
Table 5.6 Temporary malfunctions
Error text/description
Frost protection heat source monitoring source
outlet
Temperature difference of the heat source > set
value "permitted temp. difference"
This error message is deactivated as standard and
can only be activated via vrDIALOG parameter
"permitted temp. difference" (20 K difference
means deactivated).
Frost protection heat source over. source outlet
Source outlet temperature too low
(<parameter freezing protection in menu A4)
Coolant pressure too high
The integrated high pressure switch tripped at
30 bar (g).
The heat pump cannot be restarted until after 60
min. at the earliest.
Coolant pressure too low
The integrated low pressure switch tripped at
1.25 bar (g).
Coolant pressure outside the range
If the error occurs twice in a row the heat pump
cannot be started until after 60 min. at the earliest.
Operating Manual geoTHERM exclusive VWS 0020071929_00
Need help?
Do you have a question about the geoTHERM exclusive and is the answer not in the manual?