10 Technical data

11 Sensor characteristics

10 Technical data
Features
Operating voltage
Controller current consumption
Contact load of output relays (max.)
Maximum total current
Shortest switching interval
Power reserve
Maximum ambient temperature
Sensor operating voltage
Minimum cross-sections
Sensor wires
230 V power wires
Controller housing dimensions
Height
Width
Depth
Level of protection
Protection class for controller
Table 10.1 Technical data
11 Sensor characteristics
VR 10 standard sensor, type NTC 2.7 K
Sensor values
Resistance value
0 °C
9191 Ohm
5 °C
7064 Ohm
10 °C
5214 Ohm
20 °C
3384 Ohm
25 °C
2692 Ohm
30 °C
2158 Ohm
40 °C
1416 Ohm
50 °C
954 Ohm
60 °C
658 Ohm
70 °C
463 Ohm
80 °C
333 Ohm
120 °C
105 Ohm
Table 11.1 VR 10 standard sensor characteristics
24
Units
V AC/Hz
W
A
A
min
min
°C
V
2
mm
2
mm
mm
mm
mm
VR 11 standard sensor, type NTC 10 K
Sensor values
-20 °C
-10 °C
-5 °C
0 °C
5 °C
10 °C
15 °C
20 °C
25 °C
30 °C
35 °C
40 °C
50 °C
60 °C
70 °C
80 °C
90 °C
100 °C
110 °C
120 °C
130 °C
Table 11.2 VR 11 standard sensor characteristics
auroMATIC 560
230/50
max. 10
2
4
10
30
50
5
0.75
1.5
175
272
55
IP 20
II
Resistance value
97070 Ohm
55330 Ohm
42320 Ohm
32650 Ohm
25390 Ohm
19900 Ohm
15710 Ohm
12490 Ohm
10000 Ohm
8057 Ohm
6532 Ohm
5327 Ohm
3603 Ohm
2488 Ohm
1752 Ohm
1258 Ohm
918 Ohm
680 Ohm
511 Ohm
389 Ohm
301 Ohm
Installation Manual auroMATIC 560