T775A/B/M SERIES 2000 CONTROLLER
PROGRAM
RELAY 1
SETBACK
Fig. 32. Program - Setback.
Fig. 33. Program - Exit.
62-0254–03
MENU
1.2.5. SETBACK
PROGRAM
RELAY 1
The Setback temperature option displays if scheduling is
SETBACK
enabled (see Fig. 55 on page 24) or the DI Option is set to
Setback. (see Fig. 57 on page 25).
This is the desired setpoint temperature that you want to
use during setback mode for this output. For example, if
60
o
F
your setpoint is 70°F and you want the temperature to
drop 10°F during setback mode, enter 60°F as the set-
ENTER
point for this output.
SETBACK
SETPOINT
1. From the menu, use the
FOR RELAY 1
M24498
2. Use the
3. Press the
1.2.6. Program Next Output
For the next output (Mod or Relay), select the desired
output from the Program menu (see Fig. 26 on page 14).
Go to "1.2.1. SETPOINT" on page 14 to program the next
output.
When you finish programming the outputs, continue with
"1.2.7. Exiting Program Mode" on page 16.
1.2.7. Exiting Program Mode
MENU
Press the HOME button to leave programming mode and
PROGRAM
return to the home screen.
MOD 1
MOD 2
This completes the programming procedure.
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
M24499
16
and
light SETBACK.
and
buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
button to accept the value and display
the menu.
(Mod or Relay)
1. PROGRAMMING
buttons to high-