Performance Under Rated Conditions * - Model STR17G (0-100 to 0-3000 psig)
Parameter
Upper Range Limit **
Minimum Span
Turndown Ratio
Zero Elevation and Suppression
Accuracy (Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)
• Accuracy includes residual error
after averaging successive
readings.
• For F
Fieldbus use
OUNDATION
Digital Mode specifications. For
HART use Analog Mode
specifications.
*
Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
** Transmitter URL limit or maximum seal pressure rating, whichever is lower.
psig
3000
bar
210
psig
100
bar
7
30 to 1
No limit except minimum span from absolute zero to 100% of URL. Specifications valid
over this range.
In Analog Mode: ±0.15% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (300 psi), accuracy equals:
(
300 psi
±0.10 + 0.05
span psi
In Digital Mode: ±0.125% of calibrated span or upper range value (URV), whichever is
greater.
For URV below reference point (300 psi), accuracy equals:
(
300 psi
±0.075 + 0.05
span psi
Description
)
(
21 bar
or ±0.10 + 0.05
span bar
)
(
21 bar
or ±0.075 + 0.05
span bar