34-ST-03-64
Page 14
1440
1440
1200
1200
Loop
Loop
Resistance
Resistance
(ohms)
(ohms)
Figure 16—Supply voltage/loop resistance chart.
H2
Fixed
ref. leg
NOTE: Lower flange seal should not be mounted over 22 feet below or above
the transmitter for silicone fill fluid (11 feet for CTFE fill fluid) with tank at one
atmosphere. The combination of tank vacuum and high pressure capillary
head effect should not exceed 9 psi vacuum (300 mmHg absolute).
Consult Honeywell for installation of STR13D.
Figure 17—The ST 3000 transmitter with remote diaphragm seals shown mounted on a tank.
800
800
650
650
450
450
250
250
0
0
10.8
10.8
16.28 20.63 25
16.28 20.63 25
Operating Voltage (Vdc)
Operating Voltage (Vdc)
Note: A minimum of 250 ohms
Note: A minimum of 250 ohms
of loop resistance is necessary
of loop resistance is necessary
to support communications.
to support communications.
Loop resistance equals barrier
Loop resistance equals barrier
resistance plus wire resistance
resistance plus wire resistance
plus receiver resistance.
plus receiver resistance.
= Operating Area
= Operating Area
28.3
28.3
37.0
37.0
42.4
42.4
LP Side
Maximum level
Minimum level
.
HP Side
Variable
Head
H1
24249