Communications Interface Options; Optional Tracer Communications Interface; Lontalk Communications Interface For Chillers (Lci-C) - Trane R Series Installation, Operation And Maintenance Manual

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Installation - Electrical
Maximum Reset Set Points.
The equations for each type of reset are as follows:
Return
CWS' = CWS + RATIO (START RESET - (TWE -TWL))
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
Outdoor
CWS' = CWS + RATIO * (START RESET -TOD)
and CWS' > or = CWS
and CWS' - CWS < or = Maximum Reset
where
CWS' is the new chilled water set point or the "reset CWS"
CWS is the active chilled water set point before any reset
has occurred, e.g. normally Front Panel,Tracer, or ECWS
RESET RATIO is a user adjustable gain
START RESET is a user adjustable reference
TOD is the outdoor temperature
TWE is entering evap. water temperature
TWL is leaving evap. water temperature
MAXIMUM RESET is a user adjustable limit providing the
maximum amount of reset. For all types of reset, CWS' -
CWS < or = Maximum Reset.
Range
Reset
Reset
Start
Type
Ratio
Reset
10 to
Return
4 to 30 F 0 to 20 F 1%
120%
(2.2 to
16.7 C)
80 to -
50 to 130
Outdoor
80%
F
(10 to
54.4 C)
In addition to Return and Outdoor Reset, the MP provides
a menu item for the operator to select a Constant Return
Reset. Constant Return Reset will reset the leaving water
temperature set point so as to provide a constant entering
water temperature.The Constant Return Reset equation is
the same as the Return Reset equation except on selection
of Constant Return Reset, the MP will automatically set
Ratio, Start Reset, and Maximum Reset to the following.
RATIO = 100%
START RESET = Design DeltaTemp.
MAXIMUM RESET = Design DeltaTemp.
The equation for Constant Return is then as follows:
CWS' = CWS + 100% (Design DeltaTemp. - (TWE -TWL))
and CWS' > or = CWS
RTAC-SVX01J-EN
Increment
Max
IP
SI
Reset
Units
Units
1%
(0.0 to
11.1 C)
0 to 20 F 1%
1%
(0.0 to
11.1 C)
and CWS' - CWS < or = Maximum Reset
When any type of CWR is enabled, the MP will step the
Active CWS toward the desired CWS' (based on the above
equations and setup parameters) at a rate of 1 degree F
every 5 minutes until the Active CWS equals the desired
CWS'. This applies when the chiller is running.
When the chiller is not running, CWS is reset immediately
(within one minute) for Return Reset and at a rate of 1
degree F every 5 minutes for Outdoor Reset. The chiller
will start at the Differential to Start value above a fully reset
CWS or CWS' for both Return and Outdoor Reset.
Communications Interface
options

Optional Tracer Communications Interface

This option allows theTracer CH530 controller to exchange
information (e.g. operating setpoints and Auto/Standby
commands) with a higher-level control device, such as a
Tracer Summit or a multiple-machine controller. A
shielded, twisted pair connection establishes the bi-
directional communications link between theTracer
CH530 and the building automation system.
Important: To prevent control malfunctions, do not run
Field wiring for the communication link must meet the
following requirements:
All wiring must be in accordance with the NEC and
Factory
local codes.
Default
Communication link wiring must be shielded, twisted
50%
pair wiring (Belden 8760 or equivalent). See the table
below for wire size selection:
Table 44. Wire Size
10%
Wire Size
14 AWG (2.5 mm
16 AWG (1.5 mm
18 AWG (1.0 mm
The communication link cannot pass between
buildings.
All units on the communication link can be connected
in a "daisy chain" configuration.
LonTalk Communications Interface for
Chillers (LCI-C)
CH530 provides an optional LonTalk Communication
Interface (LCI-C) between the chiller and a Building
Automation System (BAS). An LCI-C LLID shall be used to
provide "gateway" functionality between a LonTalk
compatible device and the Chiller. The inputs/outputs
low voltage wiring (<30 V) in conduit with
conductors carrying more than 30 volts.
Maximum Length of Communication
Wire
2
)
5,000 FT (1525 m)
2
)
2,000 FT (610 m)
2
)
1,000 FT (305 m)
91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents