Trane Starters Engineering Bulletin page 72

Starters; electrical components; drives for centravac chillers
Table of Contents

Advertisement

Starter Options
Figure 51. PFCCs with separately controlled motor contactor
Line-side PFCC placement.
installing capacitors downstream of the motor-starter contactor. While this configuration can be
used with any type of starter, it is mandatory for all solid-state starters. Notice that the PFCCs are
connected to the line side of the main contactor (or other switching device) via a separately
controlled contactor.This separate contactor is governed by a pilot relay (PR) at/in the motor-starter
contactor or silicon controlled rectifiers (SCRs, solid-state starter applications) to switch the
capacitors on- and offline with the load.
By connecting the PFCCs through a separate contactor they do not remain connected to the motor
or the line when the motor is disconnected.This configuration prevents voltage-feedback problems
and can be used for cases where correction beyond 95 percent is desirable. Correction beyond the
manufacturer's maximum limit should not be done without consulting the manufacturer regarding
the application.
If the PFCC connections are downstream of the overloads, the capacitor leads must be routed
through the overloads as
to the motor when it is disconnected from the line.This prevents the "motor-generated voltage
buildup" described in "Rule 3" ,
72
Fusible
Safety Switch
or
Overload
Suitable Breaker
Protectors
1
2
3
Power
Circuit
Fuses
C
Enclosed 3-Phase
Capacitor Unit
Figure 51, p. 72
Motor
PR
Motor Starter
Contactor
or
Silicon-Controlled
Rectifiers (SCRs)
Figure
51, depicts an arrangement that provides an alternative to
illustrates. Notice that the capacitors are not connected
p.
71.
CTV-PRB004-EN