Electrical System–Power Wire Sizing
Table 15. MCA look-up table for 90°C copper conductors rated for 2,001–5,000 Volts
Wire Size
Note: Use this table to select line-side wiring to the starter and load-side wiring between the starter and the motor. Value in
(a) Based on 2011 NEC Table 310.60(C)(73)
Table 16. MCA look-up table for 90°C copper conductors rated for 5,001–35,000 Volts
Wire size
Note: Use this table to select line-side wiring to the starter and load-side wiring between the starter and the motor. Value in
(a) Based on 2011 NEC Table 310.60(C)(73)
60
1 Conduit
2 Conduits
3 Wires
3 Wires ea.
8
55
6
75
4
97
2
130
1
155
0
180
00
205
000
240
0000
280
250
315
350
385
500
475
750
600
table must be larger than the MCA to use the wire combination.
1 Conduit
2 Conduits
3 Wires
3 Wires ea.
6
83
4
110
2
150
1
170
0
195
00
225
000
260
0000
295
250
330
350
395
500
480
750
585
table must be larger than the MCA to use the wire combination.
3 Conduits
3 Wires ea.
360
540
410
615
480
720
560
840
630
945
770
1155
950
1425
1200
1800
3 Conduits
3 Wires ea.
390
585
450
675
520
780
590
885
660
990
790
1185
960
1440
1170
1755
(a)
(a)