Table PD-12 — Gross Cooling Capacities (MBH) 5 Ton Single Phase YHC060A1
Enter.
Dry
CFM
Bulb
61
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
56.2 48.2 64.3 37 .8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1
80
57 .6 57 .6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67 .3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6
1800
85
62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0
90
65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5
75
57 .8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37 .0 67 .3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7
80
60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47 .6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1
2000
85
64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57 .1 57 .1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5
90
67 .6 67 .6 67 .6 67 .6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8
75
59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67 .7 24.3 49.6 49.4 57 .6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1
80
62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47 .9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5
2200
85
66.0 66.0 67 .3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7
90
68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6
75
60.6 57 .4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5
80
64.0 64.0 67 .0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8
2400
85
67 .2 67 .2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67 .0 46.8 57 .2 57 .2 57 .2 57 .2 62.9 45.6
90
69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57 .1 65.5 65.5 65.5 65.5 67 .5 57 .3 62.2 62.2 62.2 62.2 63.9 57 .2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-13 — Gross Cooling Capacities (MBH) 5 Ton Three Phase YHC060A3, A4, AW
Enter.
Dry
CFM
Bulb
61
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
56.6 49.0 64.4 37 .5 67 .7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47 .0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0
80
58.5 58.5 64.6 47 .0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8
1800
85
62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67 .7 42.3 55.6 55.6 57 .3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5
90
66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1
75
58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37 .6 66.6 23.8 48.6 47 .7 57 .2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5
80
61.1 61.1 65.6 49.2 69.0 34.6 57 .3 57 .3 62.4 48.4 67 .5 34.8 53.2 53.2 57 .8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4
2000
85
64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67 .8 43.0 58.4 58.4 59.2 57 .5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0
90
67 .7 67 .7 67 .7 67 .7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3
75
59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67 .0 24.2 50.0 50.0 58.3 37 .3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0
80
63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67 .9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9
2200
85
66.4 66.4 67 .2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2
90
68.7 68.7 68.7 68.7 71.2 52.8 67 .1 67 .1 67 .1 67 .1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3
75
61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67 .3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47 .2 47 .2 53.4 36.6 61.7 21.4
80
64.5 64.5 67 .0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57 .5 57 .5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3
2400
85
67 .3 67 .3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2
90
69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67 .6 58.0 62.5 62.5 62.5 62.5 63.7 57 .9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
34
Performance
Data
85
67
73
61
85
95
67
73
61
67
(5 Ton)
High Efficiency
Ambient Temperature (F)
95
105
Entering Wet Bulb (F)
67
73
61
67
Ambient Temperature (F)
105
Entering Wet Bulb (F)
73
61
67
115
73
61
67
1 15
73
61
67
73