Current Transformer
Table 9
Overload Dip Switch Setting vs. Internal Software Gain
CPRSR RATED RLA
AS A % OF CT RATING
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
OVERLOAD DP
DECIMAL
SWITCH SETTING
SETTING
00000
00
00001
01
00010
02
00011
03
00100
04
00110
06
00111
07
01000
08
01001
09
01010
10
01011
11
01100
12
01101
13
01111
15
01111
15
10000
16
10001
17
10010
18
10011
19
10100
20
10101
21
10110
22
10110
22
10111
23
11000
24
11001
25
11001
25
11010
26
11011
27
11100
28
11100
28
11101
29
11110
30
11110
30
11111
31
SOFTWARE
GAIN
1.500000
1.483870
1.467743
1.451613
1.435483
1.403226
1.387097
1.370969
1.354839
1.338709
1.322580
1.306452
1.290323
1.258065
1.258065
1.241936
1.225806
1.209678
1.193549
1.177419
1.161291
1.145162
1.145162
1.129032
1.112903
1.096775
1.096775
1.080645
1.064516
1.048387
1.048387
1.032258
1.016128
1.016128
1.000000