Vitocontrol-S - 1 High/1 Low Temp. Heating Circuit & 1 DHW Tank

Coding

DESCRIPTION
00:6
System circuit A1 and mixing valve circuit M2, with DHW heating
35:4
4 boilers connected to Vitocontrol-S WB2B
3C:0
Gross calorific strategy (condensing) see install instructions
4C:0
Connecting on plug 20 A1: heating and circuit pump
73:7
Constantly ON
76:0
Without LON communication module
79:1
Control unit is fault manager
9d:1
With input module 0-10V; will be recognized automatically
DESCRIPTION
00:0
Boiler control connected to the cascade; this automatically occurs if 01:2 has been
programmed
01:2
Multi-boiler system with cascade control
07:1
Boiler number in multi-boiler system
2E:1
KM-bus connection of power/pump module automatically recognized
76:2
With cascade communication module; automatic recognition
82:0
Operation with natural gas
Boiler No. 2 same as Boiler No. 1 with exception to 07:2
07:2
Boiler No. 2 in multiple boiler system
Boiler No. 3 same as Boiler No. 1 with exception to 07:3
07:3
Boiler No. 3 in multiple boiler system
Boiler No. 4 same as Boiler No. 1 with exception to 07:4
07:4
Boiler No. 4 in multiple boiler system
12
VITOCONTROL-S
CODING FOR BOILER No. 1
CODING FOR BOILER No. 2
CODING FOR BOILER No. 3
CODING FOR BOILER No. 4