Fault code System character-
istics
F A6
The ionisation flame
monitor reports ex-
ternal light ingress
during the start or
after the post-purge
F A6
The ionisation flame
monitor reports ex-
ternal light ingress
during the start or
after the post-purge
F A7
No flame signal dur-
ing the safety time;
the ionisation flame
monitor reports no
flame signal
F A7
No flame signal dur-
ing the safety time;
the ionisation flame
monitor reports no
flame signal
F A7
No flame signal dur-
ing the safety time;
the ionisation flame
monitor reports no
flame signal
F A7
No flame signal dur-
ing the safety time;
the ionisation flame
monitor reports no
flame signal
F A7
No flame signal dur-
ing the safety time;
the ionisation flame
monitor reports no
flame signal
42
Cause
Measures
Gas train not gas-
Replace the gas train
tight; gas is es-
caping and burn-
ing
Incorrect para-
Set parameters; replace
meter set se-
parameter memory stick
lected
if required and enable
Ionisation elec-
Adjust the ionisation
trode incorrectly
electrode (see page 23);
adjusted; ionisa-
plug in ionisation elec-
tion cable not
trode
plugged in
Ignition electro-
Adjust the ignition elec-
des incorrectly
trodes (see page 23)
adjusted
Insulation body of
Replace the ignition
the ignition elec-
electrodes
trodes cracked
Incorrect gas type
Adjust the gas type (see
selected
page 10)
The gas train
Check the gas train and
does not open
replace if required