Manual Defrost - Honeywell PCR-300 Installation And Operating Instructions Manual

Electronic refrigeration control
Table of Contents

Advertisement

If the set temperature difference E03 is negative, an alarm is given
if it is too cold in the refrigerated area,
e.g. E03 = –10 K, cold store setpoint = –18 °C
alarm at –28 °C in refrigerated area.
If the set temperature difference E03 is positive, the alarm is given
if it is too warm in the refrigerated area,
e.g. E03 = +10 K, cold store setpoint value = –18 °C
alarm at –8 °C in the refrigerated area.
Attention: any change of the cold store setpoint valve changes also
the alarm temperature.
If E03 is set to 0, no alarm will be given.
PCR-300RC only:
E2'1 1st defrost time
E2'2 2st defrost time
E2'3 3st defrost time
E2'4 4st defrost time
E2'5 5st defrost time
E2'6 6st defrost time
Exiting programming mode: Press the
been entered.
6.6 Setting the time (PCR-300RC only)
Press and hold down the
approx. 5 seconds to access the first programming level
(Display: E00).
Setting: Press and hold down the
the time to the current time using the
(increments of 10 minutes).
Display
E00 Time
Exiting programming mode:
Press the
key several times.
––– (none), 00.1 to 23.5 hours
––– (none), 00.1 to 23.5 hours
––– (none), 00.1 to 23.5 hours
––– (none), 00.1 to 23.5 hours
––– (none), 00.1 to 23.5 hours
––– (none), 00.1 to 23.5 hours
The time is entered in increments
of 10 minutes in each case.
Caution: The times must be entered
in ascending order.
and
Setting range
00.0 to 23.5 hours
12
key after the last level has
keys at the same time for
key and change
or
key
––– (none)
01'0 hours
07'0 hours
13'0 hours
19'0 hours
––– (none)
Preset
12'0 hours