Q7300H SERIES 2000 COMMERCIAL THERMOSTAT SUBBASES
OPERATION
Refer to Table 5 for Q7300H2037 Subbase operation sequence.
System
Mode
Setting
Setting
Occupied
Any
Auto
—
On
Heat
Auto
Heat
Auto
Cool
Auto
Unoccupied Any
Any
On
a
Low speed fan is activated in the Heat mode and high speed fan is activated in the Cool mode.
Remote Temperature Sensing and Override
The Q7300H Subbase can be used with the T7147 Remote Sensor to sense temperature and provide the Occupied
mode temperature. The subbase also can be used with the T7047 Sensor if remote occupied control is not required.
®
L
W
, L
M
ON
ORKS
ON
ARK
Home and Building Control Home and Building Control
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422
62-0155—3
B.B. 3-01
Table 5. Q7300H2037 Subbase Operation Sequence.
Fan
Equipment
a
Call
—
Damper control relay energized.
—
Last system dependant . Last system is cool: call is for high
speed fan. Last system is heat: call is for low speed fan.
Stage 1
Hydronic applications: ML7984 approximately one-half
heat
open. Pump interlock relay activated to energize circulator
pump. Conventional applications: stage 1 heat is activated.
Low-speed fan is activated.
Stage 2
Hydronic applications: ML7984 is fully open.
heat
Conventional systems: no action.
Stage 1
Cooling relay activated. High-speed fan activated.
cool
—
Damper control relay de-energized.
—
System fan operates at appropriate speed with call for heat
or cool equipment.
®
, L
M
Logo and L
ON
ARK
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
Action
®