How To Read The Measurement Value Of The Built-In Temperature Sensors - Mitsubishi Electric RS232/485/LAN Serial Communication Control Manual

Rs232/485/lan serial communication control
Table of Contents

Advertisement

Message
STX (02h): Start of Message
'0'-'0' (30h, 30h): Result code. No error
'0'-'0' (30h, 30h): Operation code page number is 0
'1'-'0' (31h, 30h): Operation code is 10h (in the page 0)
'0'-'0' (30h, 30h): This operation is "Set parameter" type
'0'-'0'-'6'-'4' (30h, 30h, 36h, 34h): Brightness max value is 100(0064h)
'0'-'0'-'5'-'0' (30h, 30h, 35h, 30h): Received a Brightness setting was 80(0050h) as 80%
ETX (03h): End of Message
Check code
BCC: Block Check Code
Refer to the section 4.5 "Check code" for a BCC calculation.
Delimiter
CR (0Dh): End of packet
Repeat Step 1 and Step 2, if you need to check the Brightness setting. (Recommended)
Step 5. Request the monitor to store the Brightness setting. (Save Current Settings Command)
Header
SOH-'0'-'A'-'0'-'A'-'0'-'4'
Header
SOH (01h): Start Of Header
'0' (30h): Reserved
'A' (41h): Monitor ID
If the command should be sent to certain monitor only, the either of character 'A'(41h) to 'Z'(5Ah)
which is corresponding to monitor ID from No1 to No.26 should be set to this portion. If it is
a broad cast command(only "set command" is available), then the '*'(2Ah)should be applied.
'0' (30h): Message sender is the controller
'A' (41h): Message type is "Command"
'0'-'4' (30h, 34h): Message length is 4 bytes
Message
STX (02h): Start of Message
'0'-'C' (30h, 43h): Command code is 0Ch as "Save current settings"
ETX (03h): End of Message
Check code
BCC: Block Check Code
Refer to the section 4.5 "Check code" for a BCC calculation.
Delimiter
CR (0Dh): End of packet

6.2 How to read the measurement value of the built-in temperature sensors.

MDT652S has two built-in temperature sensors.
The controller can monitor inside temperatures by using those sensors through RS-232C.
The following shows the procedure for reading the temperatures from the sensors.
Step 1. Select a temperature sensor which you want to read.
Header
SOH-'0'-'A'-'0'-'E'-'0'-'A'
Header
SOH (01h): Start of Header
'0' (30h): Reserved
'A' (41h): Monitor ID
If the command should be sent to certain monitor only, the either of character 'A'(41h) to 'Z'(5Ah)
which is corresponding to monitor ID from No1 to No.26 should be set to this portion.
'0' (30h): Message sender is the controller
Message
STX-'0-'C'-ETX
Message
STX-'0'-'2'-'7'-'8'-'0'-'0'-'0'-'1'-ETX
(20/56)
Check code
Delimiter
BCC
CR
Check code
BCC
Delimiter
CR