  • Page 1 TPS3 Internal Manual Surge Protective Device User Manual - USA...
  • Page 2: Do Not Hi-Pot Test Spds

    WARNING - Hazardous Voltage & Shock Hazard Failure to Follow These Instructions Could Result in Death or Serious Injury • Only qualified licensed electricians should install or service SPDs • Hazardous voltages exist within SPDs • SPDs should never be installed or serviced when energized • Use appropriate safety precautions including Personal Protection Equipment • Failure to follow these instructions can result in death, serious injury, and/or equipment damage. • This manual shall be read in entirety prior to installing Bonding and Grounding Hazard Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electrical Code (NEC®) and all applicable codes. Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground in accordance with the NEC® and all applicable codes. During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage rating of the SPD and system must be verified before energizing the SPD. Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®. Do Not Hi-Pot Test SPDs Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-...
  • Page 3: Table Of Contents

    Dead front modification Instruction Changes for P1 SPD Instructions ..................4 P1 Dead Front Knockout Plate Removal Instructions ......................4 TPS3 01 Installation Instructions for: Lighting Panelboards Type P1, P2, P3 ......5 TPS3 01 Installation Instructions for: 400/600 amp S1/S2 and All SE Panels ......6 UL 1283 required language concerning the installation of EMI Filters .................7 W option Suffix: ................................7 TPS3 05 and TPS3 06 Module Replacement Instructions ............. 8 TPS3 01 and TPS3 06 Module Installation Instructions: MCC ..........
  • Page 4: Do Not Hi-Pot Test Spds

    (b) Is trained in the proper care and use of personal protective or component thereof. equipment (PPE) such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc. in accordance The sales contract contains the entire obligation of Siemens. This with established safety practices. instruction manual shall not become part of or modify any prior (c) Is trained in rendering first aid. existing agreement, commitment or relationship. Danger Unpacking and Preliminary Inspection For the purposes of this manual and product labels, DANGER...
  • Page 5: Failure To Follow These Instructions Could Result In Death Or Serious Injury

    Storage Siemens TPS3 SPDs have the following Type designations The unit should be stored in a clean, dry environment. Storage Table 1: Type Designations temperature is -55 o C (-67 o F) to +85 o C (+185 o F). Avoid exposing SIEMENS TPS3 SERIES TYPE RATING the unit to areas of high condensation. All of the packaging materials TPS3 01 & L1 Type 4 for Type 1 applications should be left intact until the unit is ready for installation. If the unit has been stored for an extended period of time, it may be necessary TPS3 05 & L5 Type 1 to clean the unit and make a complete inspection of the unit prior to TPS3 06 & L6 Type 4 for Type 1 applications installing and placing into service. For further information, please review latest editions of NEC® Art. 285, UL 1449, contact your local Siemens sales office or contact Siemens Industry Standards Changes - 2009 TPS Tech Support at (888) 333-3545.
  • Page 6: Table 2: Model Number Decoder

    Table 2: Model Number Decoder TPS SERIES DESCRIPTION TPS3 01 SPD for P1, P2, P3 Lighting and Power Distribution Panelboards, MCC and Busway TPS3 L1 10 Mode SPD for SPD for P1, P2, P3 Lighting and Power Distribution Panelboards, MCC and Busway TPS3 05 SPD for P4 & P5 Panelboards and Distribution Switchboards TPS3 L5 10 Mode SPD for P4 & P5 Panelboards and Distribution Switchboards TPS3 06 SPD for SB1, SB2, SB3, Type RCS Switchboards, MCC and Busway TPS3 L6 10 Mode SPD for SB1, SB2, SB3, Type RCS Switchboards, MCC and Busway AVAILABLE VOLTAGES VOLTAGE CODES TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 √ √ √ √ √ √ A = 240/120V Split Phase 1Ø, 3W Plus Grnd (Fig 1) √ √ √ √ √ √ B = 240/120V 3Ø, High Leg Delta (B High) (Fig 3) √ √ √ √...
  • Page 7: General Information

    This device features internal overcurrent and overtemperature within the equipment in almost any room. protection that will disconnect affected surge suppression components at the end of their useful life, but will maintain power to the load – Dead front modification Instruction Changes for P1 SPD now unprotected. If this situation is undesirable for the application, Instructions follow these instructions for servicing or replacing the device. The TPS3 unit requires a dead front opening to display its face Service of this unit consists of replacing the internal module and/or plate. Remove any installed cover from a dead front opening at the display assembly. TPS3 module location. If there is no dead front opening, follow the instructions in Fig. 2 to create an opening by removing a knockout There are no user-serviceable parts inside the replaceable module. plate.
  • Page 8: Tps3 01 Installation Instructions For: Lighting Panelboards Type P1, P2, P3

    #10-24 Slotted Hex Thread Forming Screw Torque all connections to the values as specified on the installation and maintenance instruction label affixed to the rear of the dead front. #10-32 x 5/8 Slotted Hex Therad Forming Screw Replace deadfront supports by installing screws, finger tight. Then Determine the mounting location of the TPS3 in the distribution tighten with tool. Replace trim. equipment. If it is to be mounted in the top of the distribution equipment or relocated after installation, internal phase labeling connections must be changed to ensure proper diagnostic board indication. These modifications should be made prior to installation. If...
  • Page 9: Tps3 01 Installation Instructions For: 400/600 Amp S1/S2 And All Se Panels

    TPS3 01 Installation Instructions for: 400/600 amp S1/S2 and All SE Panels If model number includes W option suffix, additional instructions follow These modifications should be made prior to installation. If the TPS3 Note that this installation is very similar to TPS3 used in S3 Panels module is field installed in the bottom, or if it is mounted in a factory except that the neutral connector is wired rather than pigtailed assembled panelboard, the internal phase label connections are and the neutral connector is at line end of the panel.
  • Page 10: Ul 1283 Required Language Concerning The Installation Of Emi Filters

    National Electrical Code regarding the appropriate size of the The circuit breaker serves as a disconnector device and overcurrent grounding conductor. protection to the connecting conductors. The TPS3 SPD includes internal overcurrent and overtemperature protective equipment. The b) The grounding conductor mentioned in item a is to be grounded breaker does not provide overcurrent protection to the SPD.
  • Page 11: Tps3 05 And Tps3 06 Module Replacement Instructions

    Lock off all power supplying this equipment before working on it. Lock off all power supplying this equipment before working on it. Open unit door and turn the internal disconnect to the off position. Open unit door and turn the internal disconnect to the off position. Remove the neutral lug wire from the disconnect switch. Remove the neutral lug wire from the disconnect switch. Remove the phase lug wires from the TPS3 05 unit. Remove the phase wires from the TPS3 06 unit lugs. Remove the TPS3 05 unit and discard properly. Remove the TPS3 06 unit with the panel and diagnostics display and discard properly. Replace unit with the new TPS3 05 unit. Replace units with the new TPS3 06 units. Attach the phase lug wires to the correct phase on the TPS3 unit. Attach the phase lug wires to the correct phase on the TPS3 06 Attach the neutral wire back to the disconnect switch. unit. Torque all connections to the values as specified on the installation and Attach the neutral wire back to the disconnect switch. maintenance instruction label affixed to the rear of the dead front. Torque all connections to the values as specified on the installation and Do not over torque disconnect switch connections as they will fail. maintenance instruction label affixed to the rear of the dead front. Turn the internal disconnect back to the on position. Do not over torque disconnect switch connections as they will fail. Close unit doors before reenergizing. Turn the internal disconnect back to the on position. Close unit doors before reenergizing.
  • Page 12: Tps3 01 And Tps3 06 Module Installation Instructions: Mcc

    Keep Out. INTERNAL DAMAGE TO TPS3 UNIT. Qualified personnel only. Do not perform dielectric or high potential Disconnect and lock off all power before tests with the TPS3 unit installed. working on this equipment. TPS3 01 and TPS3 06 Module Installation Instructions: MCC Figure 7: Installation in a MCC Mount Diagnostic Display at appropriate location Connect ribbon cables from Diagnostic Display to circuit board on Main TPS Backplane Assembly.
  • Page 13: Operation

    Operation Phase A, B & C: Green LED indicators—one per phase. Green is good. Extinguished green LED indicates loss of protection. Every suppression element in this SPD is monitored. N-G suppression element monitoring TPS3 surge protective devices require minimal attention after is logic-connected to Phase A. installation. TPS3’s contain diagnostic circuits which monitor the suppressor's status continuously and automatically. All phase indicators Service LED (red): LED illuminates in the event of problems. This and controls are located on the display panel of the unit. Display indicator is logic-connected to the Phase LEDs. Should a Phase LED...
  • Page 14: Maintenance

    HI-POTENTIAL TESTING WILL CAUSE Keep Out. INTERNAL DAMAGE TO TPS3 UNIT. Qualified personnel only. Do not perform dielectric or high potential Disconnect and lock off all power before tests with the TPS3 unit installed. working on this equipment. Maintenance Incorrectly bonded distribution systems damage SPDs. If the XO or N-G bonding jumper is not installed, the electrical system has no reference to ground. It becomes an ungrounded system. Please see previous SPDs require minimal maintenance. Periodic inspection of diagnostic...
  • Page 15: Technical Support

    Technical Support Display Replacement 1.888.333.3545 The display is field replaceable. Service should only be performed by qualified persons. Deenergize SPD, confirm with appropriate Prior to calling Siemens TPS3 Technical Support for assistance or measurement equipment and discharge internal capacitance to ordering parts, please have the following information available: ground. Mark locations and carefully disconnect diagnostic cables, contacts, connecting conductors, etc. Unbolt display and replace. TPS3 model number: ________________________________ Reinstall in reverse. Manufacture date: _________________________________ Date of Purchase: ___________________________________ Note that a sealing gasket between the display and the enclosure is Your order number: _______________________________ a key component ensuring weather resistance. Replace the gasket whenever the display is removed.