Connecting The Equipotential Bonding Circuit - Siemens PC 677B Operating Instructions Manual

Simatic industrial pc simatic panel pc 677b
Table of Contents

Advertisement

4.4

Connecting the Equipotential Bonding Circuit

A low-resistance ground connection ensures that interference signals generated by external
power supply cables, signal cables or cables to the I/O modules are safely discharged to
ground.
The equipotential bonding connection of the device is located underneath the device and is
identified by the following symbol:
Figure 4-1
Connecting the Equipotential Bonding Circuit
You require a TORX T20 screwdriver to connect the equipotential bonding conductor.
Steps for connecting the equipotential bonding
(1)
SIMATIC Panel PC 677B
Operating Instructions (Compact), 06/2008, A5E02217246-01
Equipotential Bonding
Connect the equipotential bonding connection (M4 thread) (1)
on the device (large surface, large-area contact) with the
central grounding point of the control cabinet.
The minimum permissible cross-section is 5 mm
4.4 Connecting the Equipotential Bonding Circuit
.
2
Connecting
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic 677b

Table of Contents