Burner Compartment - Roberts Gorden DUAL AIR DAT100 Installation, Commissioning, Operation & Service Manual

Heating and cooling units
Table of Contents

Advertisement

16.2 Burner Compartment

The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the gas
pipe rubber seal fully in place and all
screws fitted and tight.
16.2.1 Burner Injectors
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.
MODEL
Injector Quantity
mm dia
Injector
Size
in dia
Marking
RG P/N
mm dia
Injector
Size
in dia
Marking
RG P/N
75
12
Natural Gas (G20) and (G25)
2.71
0.1067
36
91930036
LPG Gas Propane (G31) and LPG Gas Butane (G30)
1.51
0.0594
53
91930053
SECTION 16: R
90
14
2.71
2.71
0.1067
0.1067
36
91930036
91930036
1.51
1.51
0.0594
0.0594
53
91930053
91930053
R
EMOVAL AND
EPLACEMENT
100
115
15
17
2.71
0.1067
36
36
91930036
1.51
0.0594
53
53
91930053
P
ARTS
37

Advertisement