15.2 Troubleshooting For Automatic Ignition Burner Systems

There are two burner controls used. Honeywell S4563C and
S4565C. They both have similar operating sequences. To
measure flame current, connect a 0 - 50 μA DC meter in
series with the flame probe. If the meter reads negative
values, then reverse the test leads.