Honeywell Multiple Meter Units Installation Instructions Manual page 14

Multiple meter units kwh and kwh/demand
Table of Contents

Advertisement

HONEYWELL MULTIPLE METER UNITS (MMU)
Appendix B - System Wiring Guides
PC
CHANNEL 1 OF 3
(ONE OF THREE CHANNELS
SHOWN FOR CLARITY.)
UP TO 26 IDR-16S PER
CHANNEL (3 CHANNELS
PER RS-232 KEY)
NOTE: METER 1 MUST BE INSTALLED WITHIN 100 FEET OF IDR. METERS 1-8 MUST BE INSTALLED
WITHIN 500 FEET OF IDR.
62-0400-01
Connects via
USB port on PC
IDR A-B
RJ-11
~ ~
IDR Y-Z
CONNECTION
IDR TO HONEYWELL METERS 16
IDR TO IDR
IDR TO RS-232 KEY 2000
RS-232 KEY 2000 TO COMPUTER** 8-COND. 22-26 AWG
RS-232 KEY 2000 TO MODEM **
IDR TO PULSE METER
** SUPPLIED BY HONEYWELL
NOTE: INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED
WITH THE PRE-WIRED MMU-TYPE METERING CABINETS.
NOTE: WHEN CONSTRUCTING FIELD-INSTALLED CABLES, MODULAR CABLES
MUST BE MADE SO THAT THE INDIVIDUAL WIRES GO THROUGH ON
THE SAME PIN NUMBER.
14
RJ-45
USB Key
(SUB-USBK)
AC ADAPTER
FLAT MODULAR CABLE
UP TO 4000 FEET TOTAL
STAR CONNECTION
8-COND.
6-COND.
RJ-45
RJ-45
3RD
3RD
PARTY
PARTY
METER
METER
CABLE TYPE
6-COND. 22-26 AWG
(PINS 1 & 8 NOT USED)
4-COND. 26 AWG
4-COND. 26 AWG
FLAT MODULAR CABLE
8-COND. 22-26 AWG
FLAT MODULAR CABLE
2-COND. 14-22 AWG
RJ-11
4-CONDUCTOR
DAISY-CHAIN OR
(UP TO
16 METERS)
6-COND.
RJ-45
(UP TO 16 METERS)
PARTY
METER
PAIR OF WIRES
(#22-#14 AWG)
CONNECTOR
RJ-45
RJ-11
RJ-11
RJ-45/DTE
RJ-45
3RD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmu

Table of Contents