FieldServer Omron FINS FS-8704-16 Driver Manual page 37

Fieldserver technologies computer driver instruction manual
Table of Contents

Advertisement

FS-8704-16 Omron FINS Manual
Error Message
FINS_UDP#12: Err. Mrc-Src
Reqd/Ext <%2X-%2X/%2X-%2X>
FINS_UDP#21: Err. Message from
PLC is Not a Response>
MRC <%2X> SRC <%2x> MD
<%s>
FINS_UDP#22: Err. Unknown
Device with Parameters...
Reqd/Ext dna <%d/%d> node
<%d/%d> unit <%d/%d>
FINS_UDP#23: Err. Message
Sequence Not Matched.Reqd/Ext
<%d/%d>
MRC <%2X> SRC <%2X> MD
<%s>
FINS_UDP#24: FYI. Bad
Start<%2X>
FINS_UDP#31 : FYI Net_Number
set to 1 Node <%s>
FINS_UDP#32 : FYI Udp Port is
<%d>
FINS_UDP#41: FYI. Write-thru not
Possible On MD <%s>
FINS_UDP:#51 FYI. You could
have used an Array called <%s>
to expose diagnostic info. Read
Manual.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Description and Action Required
Response from PLC not for current request.
Message from PLC for shown request is not a
response.
Response from PLC ignored because
mismatching for any shown parameters.
Response from PLC ignored because of
mismatching request-response sequence Id.
The message was ignored because the first
byte was bad.
The Net_Number parameter is 0 or not
specified. The Driver will automatically
change it to the default of 1
Information about UDP Port number in use.
Upstream device tried Write-thru operation on
other than IO memory area.
Define an array to expose stats if required.
See Appendix B.1
Page 34 of 37