b) Connection to a Closed Loop System

• Condenser water supply inlet is 1/2" female pipe thread (FPT). A minimum of 1/4" nominal
ID copper water tubing or equivalent is required for the condenser water supply line.
• Condenser return outlet is 3/8" FPT. A minimum of 1/4" nominal ID copper water tubing or
equivalent is required for the condenser return line.
• Shut-off valves and drain valves should be installed at both the condenser water supply
inlet and condenser return outlet.
• The water supply to the condenser should not drop below 4 GPM.
• The pressure differential between the condenser water supply inlet and condenser return
outlet must be no less than 10 PSIG.
• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet
temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature
must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze
cycle starts. If the condenser drain outlet temperature is not in the proper range, use a
flat blade screwdriver to rotate the adjustment screw on the water-regulating valve until
the temperature is in the proper range (rotate counterclockwise to raise temperature or
clockwise to lower temperature).
Storage Bin
Drain Outlet
3/4" FPT
Drip Tray
Drain Outlet
Stand
3/4" FPT
Minimum 3/4" Nominal ID
Hard Pipe
Fig. 6
Connection to a Closed Loop System
Minimum 1/4" Nominal ID
Copper Water Tubing
Icemaker
Icemaker Water
Supply Inlet
1/2" FPT
Condenser
Return Outlet
3/8" FPT
Vent
Tube
DCM-751BWH(-OS)
Icemaker Water Supply
Line Shut-Off Valve
Condenser Return
Line Drain Valve
Condenser Water Supply
Line Drain Valve
Condenser Water
Supply Inlet
1/2" FPT
20
Icemaker Water Supply
Line Drain Valve
Condenser Return
Line Shut-Off Valve
Condenser Water Supply
Line Shut-Off Valve
Separate piping to approved
drain. Leave a 2-inch (5-cm)
vertical air gap between the
end of each pipe and the
drain.
2-inch (5-cm)
air gap
Floor Drain