Failure code for AP422ACEAA
Central
Number
Panel
-ized
of
display
control
flashes
readout
1
01D
E1
2
02D
E2
3
11D
E3
4
12D
E4
5
10D
E5
6
14D
E6
9
05D
E9
14
15D
E4
6
26D
E6
Failure code for fix frequency outdoor unit unit(AU*EAA):
Failure description
Room temp. sensor abnormal
Indoor coil temp. sensor abnormal
Outdoor temp. sensor abnormal
Outdoor coil temp. sensor abnormal
Over-current malfunction/Power failure
High / Low pressure abnormal
Communication malfunction between indoor and wired
controller
Communication malfunction between indoor and outdoor
abnormal
Drainage system malfunction
Alarm of exterior annunciator
Coil gas pipe temp. Sensor abnormal
Temperature protection malfunction
Diagnostic code for the inverter outdoor unit
Please refers to PCB function part, page 133 and page 134.
Fault description
Fault in indoor ambient
temperature sensor
Fault
in
indoor
coil
temperature sensor
Fault in outdoor ambient
temperature sensor
Fault
in
outdoor
coil
temperature sensor
Overcurrent/
Power
failure
Fault with high pressure
Communication
error
between
indoor
and
outdoor units
Fault
in
discharging
temperature sensor
Fault with low pressure
a__
Possible cause
Sensor
is
open-circuit
short-circuit for 2min or longer.
Sensor
is
open-circuit
short-circuit for 2min or longer.
Sensor
is
open-circuit
short-circuit for 2min or longer.
Sensor
is
open-circuit
short-circuit for 2min or longer.
Detected CT current is above the
limit three times within 30min.
High pressure switch is activated
three times within 30min.
Communication error lasts 4min
or longer.
Sensor
is
open-circuit
short-circuit for 2min or longer.
Low pressure switch is activated
over 30s.
Code on wired
controller
01
02
4A
49
48
53
07
06
08
0B
03
0D
-171-
^
a`
Remedy
or
Restorable when given
corrective signal.
or
Restorable when given
corrective signal.
or
Restorable when given
corrective signal.
or
Restorable when given
corrective signal.
Restorable after repair.
Restorable after repair.
Restorable when given
corrective signal.
or
Restorable when given
corrective signal.
Restorable after repair.
Flash times of indoor
receiver board
Power LED flashes 1 time
Power LED flashes 2 times
Power LED flashes 3 times
Power LED flashes 4 times
Power LED flashes 5 times
Power LED flashes 6 times
Power LED flashes 8 times
Power LED flashes 9 times
Power LED flashes 10 times
Power LED flashes 11 times
Power LED flashes 12 times
Power LED flashes 13 times
a`