Haier Unitary smart series Service Manual page 158

Unitary smart series
Table of Contents

Advertisement

Condition for the PCB data:
1.Working ambient temperature: 10
2.Preserved ambient temperature: 20
3.Power supply:220VAC 50/60Hz voltage range:160V 250V
4.Precise of temperature control: 1
0010451167E PCB information – port and definition
P1
connect to external power supply, live line: L (220VAC)
P2
connect to external power supply, neutral line: N (0VAC)
P3 4 5 6
control external load, neutral line: N1 N2 N3 N4(0VAC)
P7
control external load, electrical heat: HEAT (control output 220VAC)
P8
control external load, health function: OXYGEN (control output 220VAC)
P9
control external load, humidification: HUMI (control output 220VAC)
P10
control external load, SWING(control output 220VAC)
P11
control external load, WATER PUMP(control output 220VAC)
P12
control external load, indoor fan motor low speed: L(control output 220VAC)
P13
control external load, indoor fan motor mid speed: M(control output 220VAC)
P14
control external load, indoor fan motor high speed: H(control output 220VAC)
P15
communication with fixed frequency single outdoor unit: COMM(0~220VAC)
P16
input control, signal live line: L'(220VAC)
P17
input control, signal neutral line: N'(0VAC)
CN1
input port of transformer (220VAC)
CN2
input port 1 of transformer (no use)
CN3
input port 2 of transformer (no use)
CN4
input port 3 of transformer (1-2 14VAC 3-4 12VAC)
CN5
input control, connecting port to wired controller: CONTROLLER three bits: 1. power supply:
12VAC, 2. power supply: 0VAC, 3. communication: COMM. .
CN6
input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE 1-2 ROOM 3-4
PIPE
Indoor ambient temp. sensor: R25=23K +-2.5% B25/50=4200K+-3% range: -40 80
Indoor coil temp. sensor: R25=10K +-3% B25/50=3700K+-3% range: -20 90
CN7
control external load, fresh air control: FRESH 1. blank, 2. power supply 0VDC, 3. control output:
12VDC.
CN8
input signal: FREEZE no use
CN9
input control no use
CN10
communication with fixed frequency single outdoor unit: (0~12VDC)
CN11
input signal, door switch: DOOR 1-2 short circuit is normal, cut off P8 output
CN12
input signal, external alarm input: ALARM 1-3 short circuit is normal, if cut off, air conditioner
stops work.
Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in short circuit, or
PCB will display failure information.
CN13
input signal, wiring port of remote receiver board: RECEIVE BOARD 1. power supply 5VDC, 2.
power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer lamp
0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC
CN14
control external load, auto elevating function
elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC
a__
70 , relative humidity:30% 95%
80
relative humidity 30% 95%
1. signal of door switch close, 2. output of
-158-
^