Advertisement

SERVICING PRECAUTIONS
AIR RECHARGING
IN COMPRESSOR
Test the refrigeration system connecting it electrically before
refilling operation. It is necessary to ascertain the function
of the motor-cempressor
and identify the defects
immediataly. If defects have been found, empty the old
system of possible R-134a residue by breaking off the end
of the extension piece at its narrow point. (Figure 1)
Replace the filter and any damaged components.
Unsolder
and pull off the piece remaining inside the service tube and
then attach an complete extension
with male Hansan and
at last, solder it to the same tube again. (Figure 2)
POINT TO BE BROKEN
SERVICE TUBE EXTENSION
Figure
1
CHARGETUBE
FEMALE
EXTENSION
HANSEN
MALE HANSEN
SOLDERING POINT
Figure
2
It is necessary to execute the soldering operation with
valve open so that the fumes caused by oil residue can
come out freely without blowholes between two tubes
dudng the beating the of the point to be soldered.
The extension fitted with the male Hansen is connected to
the female fitting of the vacuum pump tube. (Figure 3)
Air evacuating
from the system begins as soon as the
pump starts. The refrigeration
system must be kept under
vacuum until the reading on the low-pressure
gauge
indicates vacuum
(0 absolute, -1 atm., -760 mm hg) in any
case it is advisable
to keep the pump running for about 30
minutes. (Figure 3)
In case that a considerable
leakage occurs it will be
necessary to stop the vacuum pump and to add asmati
quantity of Freon to the system, if vacuum should not be
obtained (pressure gauge can't fall to 1 atmosphere),
start
the refrigeration
unit and find the leakage with the special
leak-finder.
When the defective
soldering point is visible,
re-do it after opening the extension tube valve and
reestablishing
the normal outside
pressure inside the
group.
Because the melted alley is sucked into the tubes and
block them. the pressure must be rehelanced
when
vacuum is in the system in soldedng.
As soon as the
vacuum operation is over, add the quantity in grams of
R-134a to the refrigeration
system. Remember
that every
system has an exact quanti_y of R-134a with a tolerance of
-+5grams that can be added. (Figure 4)
TO THE R-134a CYLINDER
1
STEM
Figure 4
Before performing this operation (if the vacuum pump and
refilling cylinder are connected), make sure that the valva
placed between the vacuum pump and the refilling tube are
closed in order to keep the Freon for addition to the system.
(Figure 5)
FILLING OR
VALVE TO BE OPENED
CHARGE TUBE
WHEN REFILLING
_r
TO THE REFRIGERATION
TO THE CHARGE
SYSTEM
CYLINDER
VALVE TO BE CLOSED
AFTER
VACUUM
TO THE
Figure
5
VACUUM
PUMP
In addition, check the graduated scale on the cylinder for
the quantity of R-134a to be added, for example, if we
have 750 grams of Freon in the cylinder and must add 140
grams to the group, this amount will be reached when
R-134a has dropped to 610 grams, remembering
that the
indicator shows a lower limit of meniscus.
Do this after
choosing the scale corresponding
to the gas pressure
different scales reported as the same gas pressure
indicated by the pressure gauge on the top of the column.
To make R-134a flow into the system, open the valve
placed at the base of the cylinder and connected to the
filling tube. The amount of Freon cannot be added to the
system all at once because it may cause a blocking of motor-
compressor. Therefore,
proceed by adding the original
quantity of about 20-30 grams and close the valve
immediately.
The pressure nsas and the motor compressor
must start
sucking the gas and lowering the pressure again. Regulate
the valve again, maintaining the same manner until
reaching to the quantity of R-134a established
for the
system being charged. When the system is running, the
suction pressure must be stabilized between 0.30 to
0.6(0.10 to 0.4) atmosphere.

Advertisement

Table of Contents
loading

Summary of Contents for LG LRTGC1815BK

  • Page 1 SERVICING PRECAUTIONS AIR RECHARGING IN COMPRESSOR vacuum operation is over, add the quantity in grams of Test the refrigeration system connecting it electrically before R-134a to the refrigeration system. Remember that every refilling operation. It is necessary to ascertain the function system has an exact quanti_y of R-134a with a tolerance of of the motor-cempressor and identify the defects...
  • Page 2 2000.12.6 160/120 CIRCUITDIAGRAM/SCH¢:MA DE MONTAGE WA'rF.R S UPPLYIN_ 11ME CONIROL OF_ON 31ERM0_TAT D_RO6T,TIMER '_ r--'_ QyFL'--L]TaKJ "/t • CAUIX_:Plea_Lmp_g I',epoe,_ c=_d f_om Ihet_ ou_ AVERTISSEM_iT: V_Wlbz d 6braa,_her ['8'1:I.._,,'bW,_ LL:I _2' ,11 il,L! J ----_- _ I! !, ! NONmr,&_ o'_tar,_ TIME...
  • Page 3: Parts Identification

    2. PARTS IDENTIFICATION FREEZER COMPARTMENT Freezer Shelf Automatic Ice Maker Lamp (Optional) and ice Bank (Optional) Freezer Door Bin General Type Ice Tray (Optional) Door Cooling On the refrigerator door, Freezer Temperature the cold air passageway is Control Dial installed to supply cold air to the doorside of Temperature the refrigerator...
  • Page 4: Door Switch

    3. DISASSEMBLY 3-1 DOOR 3-2 DOOR SWITCH • Freezer Door 1. To remove the door swish, pull out it with a '-' type 1. Remove the hinge cover by pulling it upwards. driver as shown in (figure 9). 2. Loosen hexagonal bolts fixing the upper hinge to the 2.
  • Page 5 3.4 FAN AND FAN MOTOR 3-6 LAMP 1. Remove the freezer sheff. (If your refrigerator have an FREEZER ROOM LAMP Ice Maker, disassemble the Ice maker first) 2. Remove the Gdlle by pulling it out and by loosening a screw. 3.
  • Page 6: Ptc-Starter

    4. ADJUSTMENT 4-1 COMPRESSOR 4-2-3 PTC-Applied Circuit Diagram 4-1-1 Role • According to Starting Method for the Motor The compressor intakes low temperature and low pressure gas evaporated from Evaporator of the Refrigerator, OVERLOAD PROTECTOR(O.L.P) condenses this gas to high temperature and high pressure gas, and then plays delivering role to Condenser.
  • Page 7: Circuit Diagram

    4-30LP (OVERLOAD PROTECTOR) CONTACTING 4-3.1 Definition of OLP POINT COVER (1) OLP (OVERLOAD PROTECTOR) is attached to the Compressor and protects the Motor by cutting the current to the Motor if the temperature dses and activates the bimetal swing in the OLP. (2) When over-voltage flows to Compressor motor, the Bimetal works by heath 9 the heater inside the OLP, and the OLP protects Motor by cutting off current which...
  • Page 8: Troubleshooting

    6. TROUBLESHOOTING 6-1 COMPRESSOR AND ELECTRIC COMPONENTS Remove the PTC- Power Source. Starter from the .__ (RatingVoltage ±10%)? "l_ Compressor measure the voltage between Terminal C of Compressor Terminals 5 or 6 of PTC. No Voltage. OLP disconnected? Replace OLP. Check connection condition.
  • Page 9: Defrost Timer

    6-2 PTC AND OLP Separate the PTC- Observation voiue is Compressor is Starter from 220V/50Hz : 228 ±30% Check another electric components. I Normaloperationof impossible or poor, Compressor 115VI60Hz : 6.88 ±30% measure the 240V!50Hz : 335 -+30% resistance between 127, 220V/60Hz : 228 No.
  • Page 10 6-4 ANOTHER ELECTRIC COMPONENTS • Cooling is impossible Check if current flows to I Cause doesn't run. i Compressor t_e following components. a. Thermostat _ Poor contacting and gas leakage. b. Starting devices _ Shorted or broken. Poor contacting c. OLP I_ or shorted.
  • Page 11: Service Diagnosis Chart

    6-4 SERVICE DIAGNOSIS CHART COMPLAINT POINTS TO BE CHECKED REMEDY Cooling • _s the power cord unplugged fTom the outlet? • Plug to the outlet. impossible. • Check if the power S/W is set to OFF. • Set the switch to ON. •...
  • Page 12 6-5 REFRIGERATING CYCLE • Troubleshooting Chart CAUSE STATE OF STATE OF THE TEMPERATURE THE SET EVAPORATOR OF THE REMARKS COMPRESSOR PARTIAL Freezer room and Low flowing sound of A little high Refrigerant level is low due LEAKAGE Refrigerator Refrigerant is heard and more than to a leak.
  • Page 13 • General Control of Refrigerating Cycle ITEMS UNIT STANDARDS REMARKS PURPOSES Pipe and Min, Pipe: within 1 hour. To protect The opening time should be reduced piping system moisture Comp: within 10 minutes. to a half of the standards dudng rain opening time Drier: within 20 minutes.
  • Page 14: Ice Maker

    7. ICE MAKER 7-1. TO INSTALL WATER PIPE 7-1-1. When connecting directly to the water tap. • Before Installation • Please confirm the following installation parts. 1. The icemaker requires the water pressure of 1.5 - 8.5kgf/cm z. (It is acceptable if city water fills a cup of 180cc with water for 3 seconds) 2.
  • Page 15 7-1-2. Connection of Pipe Connector A and B. Caution : * Feed pipe should be connected to cold water line. If it is connected to hot water line, trouble 1) Turn off main valve of water pipe. may occur. 2) Disconnect water tap from piping by loosening nuts. •...
  • Page 16 7-14, When customer uses bottled water, *If customer wants to use bottled water, extra pump should be installed as shown below. 1. The pump system should not be on the floor (it may cause noise and vibration). Securely fasten the inlet and outlet nuts of pump.
  • Page 17 7-2. STARTING THE ICE MAKER • Make sure the switch on the ice maker assy is turned "on". • Tocheck on the amountof water beingsupplied,p_ess the Test bUtCh. (Hold for 0.5 seconds) • If onlya small amount of water is putin the ice tray as water level.
  • Page 18 Water supply control switch • Adjust the water supply control switch to adjust the amount of water being supplied. • Refer to the water supply time control option table on the right to extend the supply time. SWITCH N_ SW_'H Ie_Ie_ Io_ Line indicating adequate amount of...
  • Page 19 • Clean the ice storage box and place it under the ice maker. (see the figure above) The ice storage will eventually be located on the freezer shelf. CAUTION. It takes the ice maker 24 hours to start making ice, If ice is made, the ice will be 'off taste'. If this happens, throw away the ice 2-3 times before using.
  • Page 20 7-3. TROUBLESHOOTING Operational Notes 2. The ice maker's water valve is equipped with two strainers; s plastic basket type and a wire-mesh screen. 1. The ice maker water valve contains a flow washer that Both of these can be cleaned by turning off the water acts like a pressure regulator to control the water flow.
  • Page 21 7-5 Main PWB Assembly and Parts List 7-5-1 MAIN PWB...
  • Page 22 7-5-2 Replacement Part List 870JB2039 _,MNN _-I(05-1107 D00 _ t--1.6 170JB200_2 RANS PC --:117V'Q:15'_ TA E _ TRANS WAFER _4W2_O--08 _ON P_ CON2 636J_ _W250--04 CON3 NCOM {;PIPrMP87C409_ TOSHIBA tCI(=OZZ_] 8 j _ _GULArOR IF_17e120A _EGULAT0 R ',1)BA178121 RCHM DL¢71__B JPC7812AHF 1_200_ RESET...
  • Page 23: Pwb Diagram

    7-6 PWB DIAGRAM BI,-04 ,_ T CONI _ tl_'l _'_'T t_i 7 =ITI _T T_ I T" T_,T = I '% T_T: l_ST GSN-1A _F_,"---] T _" #",_, I *.7K , Z"-- • N E--_ XOUT RESET...
  • Page 24 lOOuF 4.7KX2 /25V CON2 (REVERSE) (SDA/SO: ICE MAKER MDTOR ICE MAKER TEST S/V oc_o_ __7_ 6*2KF ICE MAKER SENSBR (AIN71 104_ CON101 SUPPLYING S/_/) (WATER TIME CONTROL 4_10.12,13,16,24,25,26...
  • Page 25: Exploded View And Replacement Parts List

    8. EXPLODED VIEW & REPLACEMENT PARTS LIST • The parts of refrigerator and the shape of each part are subject to change in different localities. • Capacitors and fuse are optional parts. GR-T622, GR-T722 * : Option...
  • Page 26 * : Option...
  • Page 27 ICE MAKER PART * : Option &...

This manual is also suitable for:

Lrtgc1815bsLrtgc1815wGr-t622Gr-t722

Table of Contents