General Information; Safety Considerations - Nordyne 13 SEER User's Information And Installation Instructions Manual

13 seer r-410a high efficiency split system
Table of Contents

Advertisement

The continuous indoor blower operation can be
obtained with the thermostat
system switch set
in any position, including OFR
The continuous
indoor
blower
operation
is
typically
used to circulate
the indoor
air to
equalize a temperature
unbalance due to a sun
load, cooking, or fireplace operation.
To Maintain Your Air Conditioner --
CAUTION:
Be certain
the electrical
power
to
the
outdoor
unit and
the furnace/
air handier
is disconnected
before
doing
the following
recommended
maintenance.
1. Regularly:
a,
Clean or replace the indoor air filter at the
start of each heating and cooling season,
and when an accumulation
of dust and dirt
is visible on the air filter.
b,
C,
Remove any leaves and grass clippings
from the coil in the outdoor
unit, being
careful not to damage the aluminum fins.
Check for any obstruction,
such as twigs,
sticks, etc.
2.
Before Each Cooling Season:
If the furnace/air
handler blower motor and
the outdoor unit fan motor(s) have oil tubes
at the motor bearings,
apply 10 drops of
SAE No. 20 motor oil to each oil tube.
CAUTION:
Do not
over=oil,
or oil
motors
not
factory=equipped
with oil tubes. The
compressor
is hermetically
"sealed"
and does not require lubrication.
=
Before Calling a ServiceTechnician,
Be
Certain:
a,
The unit thermostat
is properly
set --
see "To Operate Your Air Conditioner
for
Cooling" and "To OperateYour
Furnace for
Heating."
1. GENERAL
INFORMATION
Read the following instructions completely before
performing the installation.
CAUTION:
This unit uses refrigerant
R=410A. DO
NOT under any circumstances
use
any other refrigerant
besides
R=410A
in this unit. Use of another
refrigerant
will damage this unit.
Condensing
Unit Section
-- Each condens-
ing unit is shipped
with a refrigerant
charge
adequate
to operate the outdoor section with
an indoor matching coil or air handler, and 15
feet of refrigeration
line.
NOTE: DO NOT USE ANY PORTION OF THE
CHARGE
FOR PURGING
OR LEAK TEST-
ING.
Matching coils and air handlers are shipped with
a small pressurized holding charge to pressurize
them to keep out contaminants.
To release the
pressure,
read the indoor section
installation
instructions
carefully.
Liquid and Suction
Lines--
Refrigerant grade
copper tubing should be used when installing the
system. Refrigerant
suction line tubing should
be fully insulated.
Field
Connections
for
Electrical
Power
Supply
-- All wiring must comply with current
provisions of the "National Electrical Code" (ANSi
C1.) and with applicable
local codes having
jurisdiction.
The
minimum
size of electrical
conductors
and circuit protection
must be in
compliance with information listed on the outdoor
unit data label.
2. SAFETY
CONSIDERATIONS
Pressures
within
the System -- Split system
air conditioning
equipment
contains liquid and
gaseous refrigerant under pressure, installation
and servicing of this eq uipment should be accom-
plished by qualified, trained personnel thoroughly
familiar with this type of equipment.
Under no
circumstances
should the Homeowner
attempt
to install and/or service the equipment.
b. The unit disconnect
fuses are in good
condition,
and the electrical power to the
unit is turned on.

Advertisement

Table of Contents
loading

Table of Contents